LONG BRACKET INSTALLATION
1. Remove bracket from junction box, pull through
leads to connector block. Attach ground wire to
grounding screw.
2. Remove Connector block from threaded adapter,
pull leads through to connect wires to correct
wires on block. Black lead is "line" lead and "white"
lead is "neutral."
3. Push block into place and tighten screws. Install
fixture. NOTE: Plugs should be removed and
resealed with pipe sealant.
Disconnect supply circuit before opening fixture.
CAUTION:
To maintain maximum light output from this fixture, it should be cleaned periodically as follows:
•
1. Alkaline or acidic cleaners will attack the protective coating of epoxy on the fixture and should not be used.
The aluminum exterior of this fixture should be cleaned only with a mild soap or cleaner, and should
be rinsed with water immediately. This will allow the epoxy to protect the fixture from corrosive elements in
the atmosphere and result in longer fixture life.
2. The glass globe should be cleaned using a soft cloth and a non-abrasive cleaner. The globe should be
regularly inspected for scratches or chips. If the globe is scratched or chipped, it must be replaced.
3. The porcelain enamel reflector may be cleaned with any non-abrasive detergent or glass cleaner.
These periodic cleaning procedures are important to prevent the accumulation of dust and dirt which will
•
impair the light output of the fixture.
When removing and repairing the fixture, lubricate threads only with Appleton TLC-3 conductive, high
•
temperature lubricant. This should only be necessary if threads are no longer coated with the blue or black
color of the dry film lubricant.
See the next page for drawings and a complete parts list.
•
The fixture must be operated in an environment that does not exceed 55°C.
•
The fixture may be operated on AC power only up to 277 VAC and 300 VDC.
•
WARNING:
To reduce the risk of fire or explosion, do not install where the operating temperature exceeds
•
ignition temperature of hazardous atmospheres.
Refer to the nameplate on the fixture for maximum operating temperature and for proper
•
fixture classification.
Appleton • 1.800.621.1506 • www.appletonelec.com
#10-24 x 3/8"
SL.RD.HD.
SET
SCREW
MAINTENANCE DATA
OPERATIONAL DATA
JUNCTION
BOX
TLC-3 HERE
59064050000
THREADED ADAPTER
VPT-7 CONNECTOR BLOCK
SCREW #8 -32 x 1/2" PH. HD.
650590-000 Rev. B 07/17/18 • Page 2 of 8