Troubleshooting
Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite Customer Service at (773) 869-1234
before returning your unit for service.
SYMPTOM
No AC Output
(All Indicator Lights are OFF)
Battery Not Recharging
(AC Input Present)
All Three "BATT VOLT/CHRG CURR"
LEDs are slowly flashing (½ second
flashes) with Operating Mode Switch
in the "AUTO/REMOTE" position.
All Three "BATT VOLT/CHRG CURR"
LEDs are rapidly flashing (¼ second
flashes) with Operating Mode Switch
in the "AUTO/REMOTE" position.
Red "LOW" Battery Indicator Light is
flashing with Operating Mode Switch
in the "AUTO/REMOTE" position.
Red "LOAD" Operation Indicator
Light flashing
* User-supplied.
PROBLEMS
Unit is not properly connected to utility power
Operating Mode Switch is set to "DC OFF" and AC
input
is present.
This is normal when the Operating Mode Switch is set
to
"CHARGE ONLY" and AC input is absent.
Output circuit breaker is tripped.
Unit has shut down due to battery overcharge
(preventing battery damage). The problem may be with
connected auxiliary chargers, if any, or with the unit's
charger.
Unit has shut down due to excessive battery
discharge.
Connected batteries are dead.
Unit has shut down due to overload.
Connected batteries are dead.
Battery fuse* is blown.
Battery cabling* is loose.
Unit has shut down due to battery overcharge
(preventing battery damage). The problem may be with
connected auxiliary chargers, if any, or with the unit's
charger.
Charger Enable/Inhibit Switch inadvertently set to
"INHIBIT".
Charger circuit breaker is tripped.
Battery is excessively discharged. Unit will shut down
to prevent battery damage.
Battery is overcharged. Unit will shut down to prevent
battery damage. The problem may be with connected
auxiliary chargers, if any, or with the unit's charger.
Battery voltage is low. Unit has shut down to protect
battery from damage.
False reading due to undersized or insufficiently
connected DC cabling
Inverter is overloaded. Unit will automatically shut
down after 5 seconds.
CORRECTIONS
Connect unit to utility power.
Set Operating Mode Switch to "AUTO/REMOTE" or "CHARGE ONLY"
No correction is required. AC output will return when AC input returns.
Set Operating Mode Switch to "AUTO/REMOTE" if you require AC
output.
Reset circuit breaker.
Disconnect any auxiliary chargers. Reset by moving Operating Mode
Switch to "DC OFF". Wait 1 minute and switch to "AUTO/REMOTE" or
"CHARGE ONLY." If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.
Use an auxiliary charger* to raise battery voltage. Check external
battery connections and fuse. Unit automatically resets when
condition is cleared.
Check and replace old batteries.
Reduce load. Reset by moving Operating Mode Switch to "DC OFF".
Wait 1 minute. Switch to "AUTO/REMOTE" or "CHARGE ONLY".
Check and replace old batteries.
Check and replace fuse.*
Check and tighten or replace cabling.*
Disconnect any auxiliary chargers. Reset by moving Operating Mode
Switch to "DC OFF". Wait 1 minute and switch to "AUTO/REMOTE" or
"CHARGE ONLY." If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.
Set Charger Enable/Inhibit Switch to "ENABLE".
Reset circuit breaker.
Use an auxiliary charger* to raise battery voltage. Check external
battery connections and fuse. Unit automatically resets when
condition is cleared.
Disconnect any auxiliary chargers. Reset by moving Operating Mode
Switch to "DC OFF". Wait 1 minute and switch to "AUTO/REMOTE." If
unit remains in shutdown mode after several attempts to reset,
contact Tripp Lite Customer Service for assistance.
If AC power (utility- or generator-supplied) is present, the unit will
automatically reset itself and start recharging connected batteries.
However, if an external charger is used to recharge the batteries, you
will need to manually reset the unit by moving the Operating Mode
Switch to "DC OFF" for two seconds then returning it to "AUTO/
REMOTE".
Use sufficient size DC cable sufficiently connected to Inverter/Charger.
Reduce load. Reset by moving Operating Mode Switch to "DC OFF".
Wait 1 minute. Switch to "AUTO/REMOTE" or "CHARGE ONLY".
11