14.2.2 If password is set
1
2
3
4
5
6
to
38
14.2.3 If any parameter is found to be incorrect during verification
14.3
functional test
The user is responsible to make a functional test after verification of the safety
parameters. The procedure for periodic proof test described in section 10 shall
be used.
In addition, if a process calibration is taken into SIL-mode operation (refer to
section 13.3 - Advanced functions), it is mandatory that the accuracy of the device
(and sensor, if applicable) are tested.
15 fault reaction and restart condition
When the 9113 detects a fault the output will go to Safe State, in which the output will go to
"de-energised".
If the fault is application-specific (cable error detection) the 9113 will restart when the fault
has been corrected.
For device faults there are 2 ways of bringing the device out of Safe State.
1. Power cycle the device.
2. Bring the device out of SIL mode (choose "NO" in the menu point "EN.SIL"), and set it back
to SIL mode again (choose "YES" in the menu point "EN.SIL" and verify the configuration).
9113 TemperaTure / ma CONVerTer
action
Press OK
Enter password and press OK
Set ADV.SET to Yes and press OK
Set SETUP to SIL and press OK
Set EN.SIL to YES and press OK
(At this time the device starts operating
in SIL mode with the entered configuration
parameters!)
As step 6 to 38 for 14.2.1
* Open is shown briefly in the display
Remove SIL-mode (by entering the password and selecting SIL-mode
OFF).
Go through the setup menu and correct the parameter(s).
Repeat step 1 to 38 (with correct parameters).
Version No. V6R0
Safety manual
Display shows
PASSW
ADV.SET
SETUP
EN.SIL
CONFIG
Verify
OPEN->LOCK*
As step 6 to 38 for
14.2.1
17