LERBAKKEN 10, 8410 RØNDE DENMARK
9113
For safe installation of 9113B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
4501
For Installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PRelectronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
c-FM-us Certificate: ....................................................3038279
Hazardous Classified Location
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC
or Class I, Zone 0/1 Group IIC, [Ex ia] IIC
Intrinsically safe apparatus
entity parameters:
Vmax (Ui) Vt (Uo)
Imax (Ii)
It (Io)
Pi Po
Ca C
+ Ci
cable
La L
+ Li
cable
The sum of capacitance and
inductance of cable and
intrinsic safe equipment must
be less or equal to Ca and La
Revision date:
2012-06-07
32
FM Installation drawing
Version Revision:
V4 R0
9113 - Product Version 9113-004
Unclassified Location or
Hazardous Classified Location
Class I, Division 2, Group A,B,C,D T4
or Class I, Zone 2 Group IIC T4
-20 ≤ Ta ≤ 60ºC
4501
44
43
42
41
54
53
52
51
9113
91 92 93 94 95
Power
Rail
Prepared by:
PB
9113QF01
34
33
32
31
14
13
12
11
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
: 253 V, max 400 Hz
m
Page:
1/3