Briggs & Stratton GC1030 Serie Mode D'emploi page 16

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Level 0
Level 1 (On screen)
Frequency
Monitoring
(FREQ MONITOR)
Current Monitoring
(CURRENT
MONITOR)
Load Monitoring
(LOAD MONITOR)
Level 2 (On screen)
* Under-voltage Warning
(UNDER VOLT WARNING)
* Under-voltage Warning
Threshold
(UV WARNING THRESHOLD)
* Over-voltage Shutdown
(OVER VOLT SHUTDOWN)
* Over-voltage Shutdown
Threshold
(OV SHUTDWN THRESHLD)
* Over-voltage Warning
(OVER VOLT WARNING)
* Over-voltage Warning
Threshold
(OV WARNING THERSHOLD)
* Under-frequency Shutdown
(UNDER FREQ SHUTDOWN)
* Under-frequency Shutdown
Threshold
(UF SHUTDWN THRESHLD)
* Under-frequency Warning
(UNDER FREQ WARNING)
* Under-frequency Warning
Threshold
(UF WARNING THRESHOLD)
* Over-frequency Shutdown
(OVER FREQ SHUTDOWN)
* Over-frequency Shutdown
Threshold
(OF SHUTDWN THRESHLD)
* Over-frequency Warning
(OVER FREQ WARNING)
* Over-frequency Warning
Threshold
(OF WARNING THRESHOLD)
* CT Ratio
(CT RATIO)
* Over-current Action
(OVER CURR ACTION)
* Over-current Threshold
(OVER CURR THRESHOLD)
* Over-current Delay
(OVER CURR DELAY)
* CT Location
(CT LOCATION)
* Generator Rating
(GEN RATING)
* Over-load Action
(OVERLOAD ACTION)
* Over-load Threshold
(OVERLOAD THRESHOLD)
Parameters (On screen)
Disable/Enable
55 – 300 Volt Ph-N
Disable/Enable
105 – 350 Volt Ph-N
Disable/Enable
100 – 345 Volt Ph-N
Disable/Enable
10.0 – 59.0 Hz
Disable/Enable
11.0 – 60.0 Hz
Disable/Enable
26.0 – 75.0 Hz
Disable/Enable
25.0 – 74.0 Hz
0 – 8000 / 5
None/Notification/Warning/
Electrical Trip/Shutdown
5 – 10000 Amp
1 – 600 sec
On Load Cable/On Alt Output
Cable
0 – 8000 kW
None/Notification/Warning/
Electrical Trip/Shutdown
50 – 150 %
Page | 10