Briggs & Stratton GC1030 Serie Mode D'emploi page 15

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Level 0
Level 1 (On screen)
(GENERAL TIMER)
Generator
(GENERATOR)
Voltage Monitoring
(VOLT MONITOR)
(SAFETY MONITOR DELAY)
Alternator
Configuration
(ALT CONFIG)
(PHASE REVERSE DETECT)
(PHASE REVERSE ACTION)
* Genset Nominal Frequency
(UNDER VOLT SHUTDOWN)
(UV SHUTDWN THRESHLD)
Level 2 (On screen)
Mains Detect Delay
(MAINS DETECT DELAY)
* Alternator Detect Delay
(ALT DETECT DELAY)
Warm-Up Delay
(WARM UP DELAY)
Return To Mains Delay
(RETN-TO-MAINS DELAY)
* Engine Cooling Time
(ENG COOL TIME)
* Stop Action Time
(STOP ACTION TIME)
* Additional Stopping Time
(ADDN STOPPING TIME)
Load Transfer Delay
(LOAD TRANSFER DELAY)
Power Save Mode Delay
(PWR SAVE MODE DELAY)
Sounder Alarm Time
(SOUNDER ALARM TIMER)
Auto Exit Config Mode
(AUTO EXIT CNFG TMR)
* Alternator Present
(ALT PRESENT)
* Number Of Poles
(NUMBER OF POLES)
* AC system
(ALT AC SYSTEM)
* Min Healthy Voltage
(MIN HEALTHY VOLT)
* Min Healthy Frequency
(MIN HEALTHY FREQ)
* Phase Reversal Detection
* Phase Reversal Action
* Auto Load Transfer
(AUTO LOAD TRANSFER)
* Genset Nominal Voltage
(NOMINAL VOLTAGE (L-L))
(NOMINAL FREQUENCY)
* Under-voltage Shutdown
* Under-voltage Shutdown
Threshold
Parameters (On screen)
1 – 300 sec
1 – 60 sec
0 – 60 sec
0 – 600 sec
0 – 300 sec
10 – 120 sec
0 – 120 sec
0 – 60 sec
5 – 1800 sec
1 – 300 sec
10 – 1800 sec
No/Yes
2/4/6/8
Single Phase 2 Wire/ Single
Phase 3 Wire/ Three Phase 4
Wire (1Ph 2 wire/1Ph 3
wire/3Ph 4 wire)
50 – 350 Volt Ph-N
10 – 75 Hz
Disable/Enable
None/Notification/Warning/
Electrical Trip/Shutdown
Disable/Enable
100 – 650 Volt L-L
10.0 – 75.0 Hz
Disable/Enable
50 – 295 Volt Ph-N
Page | 9