Terminal
Description
TAMPER R
Tamper outputs for (Wall and cover tampering). The connection of these
terminals depends on the setting of the TAMPER jumper:
TAMPER F
INT: Connect the F to the COM (No connection to R terminal).
EXT: Connect the R and the F to a zone input.
1 PIN Only: Connect the R and the F to a zone input EOL. (An internal 2.2 K
EOL resistor is connected in serial to the output)
PROX
Connect these terminals to a zone input for the indication of Anti approach
(N.C)
alarm. (Stand Alone mode only)
NOTE:
You can connect the PROX terminals in serial to the TAMPER terminals in order to have
a single tamper indication from the sounder.
TRBL
The trouble output is activated (closed) according to a trouble defined by the
setting of the trouble DIP-switch (CONFIG 1).
(N.O)
C+
Terminal to positive, sounder is silent.
Terminal open, sounder is activated.
C-
Terminal to negative, sounder is silent.
Terminal open, sounder is activated
ST
Terminal to negative, strobe is activated.
Terminal open, strobe is deactivated.
NOTES:
1.
The sounder will not operate when a battery is not connected or no power supply is connected to the
PS terminals.
2.
After powering-up the sounder, it will not operate for a period of 20 seconds (sound and strobe) in
order to avoid accidental activation during installation.
3.
After powering-up the sounder, the sounder inputs (C- or C+) will cause activation only if they have
been in normal (silent) state at least for 10 seconds.
4.
The PROX and TRBL outputs are deactivated in BUS mode configuration.
5.
To protect the battery against deep discharge, the battery will be automatically disconnected below
10.5 VDC.
TAM PER
INT EXT
Tam per Output
(0.5A, 24V N.C)
Anti Approach
(To Int.
Output
Tam per)
(0.1A, 24V N.C)
Trouble Output
70 m A m ax
+ 12 V
COM (-)
COM (-)
Figure 1 – Stand Alone Configuration
Optional
To
13.8VDC
Battery
1.6 A
BLK
RED
TRIG STRO B
POW ER
C -
AUTO
C +
M AN
ON
ON
1
2
3
4
1
2
3
4
CONFIG
ID1
LED2
7
To Internal
Speaker
13.8VDC ,
200 m A (m ax)
Status LED2
On/Off