GB
RESET FUNCTION (option 010 606)
The RESET function helds output pressure at 0 bar, as long as pin L stays in logic value 0.
As long as pin L (ENABLE) is maintain at logic value 0, the valve output pressure remains at 0 bar.
All bit combination settings at the input are ignored and the valve remains at 0 bar.
If pin L (ENABLE) goes to logic value 1, the output pressure is updated in relation to the input binary combination given at
that moment. If the bits combination changes and if pin L (ENABLE) is held at logic 1, the valve output pressure is modified
in relation to this new combination.
As long as the enable line is held at "low", the output pressure is 0 bar, and all data is ignored.
If the enable line is held at "high", the output pressure is updated according to the bit combination at the input.
Set point
Enable
18
All manuals and user guides at all-guides.com
Output pressure
at 0 bar