Function and features
• The controller
(both in accordance with the AS-i version 2.1), a mini controller and a
CANopen interface
• It controls the exchange of data to the sensor /actuator level
• processes the peripheral data in the integrated processor (signal
preprocessing)
• works as stand-alone controller with exchange of data to the PC
(visualisation)
• communicates with the higher control level (in the gateway mode)
Programming interface RS232C
• Baud rate 4800 to 115,200 baud
• Max. distance between controller
• Potential separation from the controller
• Programming cable E70320 for connection to host required
CANopen interface
• Baud rate 10k, 20k, 50k, 125k, 250k, 500k, 800k, 1Mbits/s
• Max. distance between controller
rate
• Potential separation from the controller
• Up to 127 controllers connected in parallel
• Pin connection: Pin 1: V-; Pin 2: CAN_L; Pin 3: Shield;
Pin 4: CAN_H; Pin 5: V+
Installation
Fix the controller
is IP20, therefore it should be mounted in a protected location (e.g.
control cabinet).
Ensure a condensation-free environment. Avoid excessive dust,
vibration and shock. The air circulation through the vents must
not be impeded.
Avoid installation in direct vicinity of frequency converters.