NOT E
The rear of the indoor unit can be installed flush against the wall.
Air
discharge
Min. 50 cm
Side view
Concealed-Duct Type / 2-Way, 4-Way Semi-Concealed Type
1-Way Semi-Concealed & Slim Type
Semi-Concealed Type
Ceiling
Min. 5 cm
Obstacle
Air
discharge
Air
Wall
intake
Min. 5 cm
Floor-Standing, Concealed Floor-Standing Type
Min.
10 cm
Min. 100 cm
Horizontal view
Wall-Mounted Type
* Min.
15 cm
Front View
*SPW-K075/095/125XH: Min. 5 cm
Air intake
Max. 25 cm
Obstacle
Fig. 2-1-2
1 m
1 m
1 m
Semi-Concealed Slim Type
Wall
100 cm
20 cm
100
cm
Min.
10 cm
Min. 100 cm
Vertical view
Min. 15 cm
* Min.
15 cm
● The distance between the indoor unit and any obstructions
should be as shown in the figure below.
● If installing in a highly humid location, give consideration to
preventing condensation on the main unit.
SA
RA
Distance to
obstruction
1 m
1 m
N OT E
There is a packaging bracket located on each of the four
product corners. Remove these brackets from the product.
Fig. 2-2
20 cm
20 cm
2-2. Outdoor Unit
AVOID:
Fig. 2-3
● heat sources, exhaust fans, etc. (Fig. 2-8)
● damp, humid or uneven locations
● indoors (no-ventilation location)
DO:
● choose a place as cool as possible.
● choose a place that is well ventilated.
● allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 2-9)
Fig. 2-4
Fig. 2-5
19
Heat Exchanger
Electrical component box
70 cm
External thread
L-shape bracket
Hot air
Out-
door
unit
Distance to obstruction
80 cm
EA
OA
Fig. 2-6
Fig. 2-7
Exhaust fan
Heat source
Fig. 2-8