Maintain a 12" (30.5 cm) minimum
space around the units.
Control Cable Input
3/4" (1.9 cm) Min
5. Install the Steam Generators
WARNING: Risk of property damage. Allow a minimum of 12" (30.5 cm) of air space around the
steam generators at all times. This provides an area for the heat generated by the units to dissipate.
NOTICE: For optimum performance, install the steam generators as close as possible to the steam heads.
The steam generators must be installed within 25' (7.62 m) of the steam head.
Install the desired drain pan at the steam generator location.
Position the steam generators on the drain pan.
1059059-2-E
12"
(30.5 cm)
Drain Pan
Pressure Relief Valve
Inlet
Drain (install per
applicable codes.)
Steam Outlet
8
Kohler Co.