G
®
HYGRASGARD
The humidity ⁄ temperature sensor HYGRASGARD
the relative humidity and ⁄ or temperature of air. It converts the measurands
humidity and temperature into standard signals of 0 -10 V. Relative humidity (in
% r. H.) is the quotient of water vapour partial pressure divided by the saturation
vapour pressure at the respective gas temperature. HYGRASGARD
RFTF-UP are applied in non-aggressive dust-free ambiences in refrigeration, air
conditioning, ventilation and clean room technology, in residential rooms, offices,
hotels, technical rooms, meeting rooms and convention centres. These measuring
transducers are designed for exact detection of air temperature and humidity.
A digital long-term stable sensor is used as measuring element for humidity and
temperature measure ment.
TECHNICAL DATA:
Power supply: ........................ 24 V AC ⁄ DC
Power consumption: ................ < 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
Sensors: ............................... digital humidity sensor with integrated
HUMIDITY:
Measuring range, humidity: ....... 0 ...100 % r. H.
Operating range, humidity: ....... 10 ... 95 % r. H.
Deviation, humidity: ................. ± 5 % r. H., at +20 °C
Output, humidity: .................... 0 -10 V
TEMPERATURE:
Measuring range, temperature: ....... 0....+50 °C
Operating range, temperature: ....... 0....+50 °C
Deviation, temperature: ........... ± 1 K, depending on place of installation and
Output, temperature: .............. 0 -10 V
Ambient temperature: ............. storage - 25 ...+50 °C, operation - 5 ...+50 °C
Electrical connection: .............. 3- or 4-wire connection (see connecting diagram),
Installation: ........................... in in-wall flush box Ø 55mm
Long-term stability:................. ± 1 % per year
Protection class: .................... III (according to EN 60 730)
Protection type: ..................... IP 20 (according to EN 60 529)
Standards: ............................ CE conformity, electromagnetic compatibility
SWITCH PROGRAMME:
Manufacturer: .......................... Busch-Jaeger Reflex Si
Enclosure: ............................. plastic, standard colour alpine white (similar RAL 9010)
Type ⁄ WG1
Designation
RFF - UP - U
R F F - U P - U
RFTF - UP - U
R F T F - U P - U
RFF - UP ⁄ RFTF - UP
®
RFF-UP ⁄ RFTF-UP measures
temperature sensor, dew-proof, small hysteresis,
high long-term stability
(output corresponding to 0 -10 V)
(output corresponding to 0 -10 V)
mounting position also greater
0.14 - 1.5 mm² via plug terminals
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC
(other switch programmes, manufacturers, colours
and prices upon request)
(other colours are possible on request with colour variants
depending on the respective light switch programme)
Measuring Range ⁄ Readout
Humidity
Temperature
0 ...100 % r. H.
0 ...100 % r. H.
0...+50 °C
Connecting diagram
®
RFF-UP ⁄
In case of output 0 -10 V, GND connections (1)
and (3) are connected on the circuit board.
Connecting diagram
In case of output 0 -10 V, GND connections (1)
and (3) are connected on the circuit board.
Output
Humidity
Temperature
0 -10 V
0 -10 V
0 - 10 V
4
4
Output
3
relative
humidity
3
0-10V
GND
UB -
GND
UB +
2
2
1
1
8
8
4
4
Output
Output
3
temperature
relative
0-10V
humidity
3
0-10V
GND
UB -
UB +
GND
2
2
1
1
Item No.
U - variant
1201-5111-0008- 180
U - variant
1201-5111- 1000- 017
RFF - UP - U
RFTF - UP - U