Allegion MG600-2 Serie Installation page 3

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation - Electical
1.
Position the power selector jumpers according to the input voltage, then finish electrical connection to the door operator.
2.
When the maglock assembly and armature/strike plate are mated, the junction is Normally Open and the LED will turn to green.
3.
The remaining three terminals of the terminal block (COM/ NO/ NC) provide an auxiliary relay output which can be used as a door position
switch.
MAGLOCK PCB
(MG600 Left PCB Shown)
-
+
Timer
0-90 sec
Optional
Feature
L.E.D.
CAUTION
Unit may work if jumpers are
incorrectly installed, but will draw
a higher current and may possibly
damage the assembly.
Typical Installation
** Important: Install the armature plate with the flexibility to automatically adjust its position with the magnet.
Power Selector
Jumpers:
(default) (optional)
DOOR POSITIONING SENSOR
Power
Supply
Dry
Contact
* When "SW" is OFF, the Door Status
Sensor (REED SWITCH) detects if the
door is well closed.
DOOR SENSOR (Reed SW.)
BLACK
Reed switch dry contacts are
rated max 3w (max switching
contact 0.25 A) for safe operation.
Do not exceed the rating.
NC
RED
C
NO
GREEN