Connection rules and regulations
- The device must be supplied with 230V single-phase current at 50Hz.
- The device's power supply must be directly connected to the main
supply after the circuit breaker without any intermediate switch.
- The device's power cable must be connected to the main supply via a
connection box. In damp areas, such as bathrooms and kitchens, the
connection box must be installed at least 25cm above the floor.
- An Earth connection is prohibited. Do not connect the pilot
wire (black wire) to Earth.
- Power must be directly connected to the grid after pole disconnec-
tion device in accordance with the installation requirements.
- If the power cable is damaged, it must only be replaced by an electrician.
- If you are using the pilot wire and it is protected by a 30mA differential
(e.g.: bathroom use), the pilot wire's power supply must also be protec-
ted on this differential.
This device must be installed with a remotely controllable
programming system. This type of system can be connected
via the pilot wire of the device
Wiring diagram for the heating panel
- Cut off the power supply and connect the wires as shown in the fol-
lowing diagram:
CONNECTING THE DEVICE
23