Voltage Test with RCD Trip Test

During voltage tests in systems equipped with RCD, a
RCD can be tripped at a nominal residual current of
10mA or 30mA.
For this the voltage between L and PE is tested and both
push buttons (6 and 9) must be pressed. The RCD will
tripp.
Phase rotation Indication
The voltage testers are equipped with a double-pole
phase rotation indicator.
The safety measures have to be met.
The rotary phase indication is always active. The symbol
(4) is always displayed. However, the phase rotation
can only be determined within a three-phase system.
Here, the instrument indicates the voltage between two
external conductors.
1)
Connect the instrument test probe (2) with the sup-
posed phase L2 and the handle test probe (1) with
the supposed phase L1.
2)
Embrace both handles completely
Signifies that the supposed phase L1 is the actual phase
L1 and the supposed phase L2 is the actual phase L2,
phase rotation is right, the LED
When re-testing with exchanged test probes the LED
(4) should not illuminated.
(4) is illuminated.