Fig. 37
Change to 'STORE YES' with Arrow down (no. 3) or Arrow up (no. 4) and Confirm (no. 2).
You will then return to the standard display and the AKS 4100 is now running with optimised
parameters.
Note: After changing the parameters, do NOT run a quick set-up. If you do so, you will need to fill in the
parameters again.
If you make a new set-up, please fill in the set-up parameters in the table, and add them to your
logbook.
Installation
date:
Probe
CO
2
Probe length
4 mA scale
20 mA scale
AKS 4100
Gas constant 2.5.3
280 mm
Blocking distance 2.3.2
Time constant 2.3.3
Level threshold 2.5.7
Full area 4.1.1
Empty area 4.1.2
ICAD
ICAD speed i04
UniSAB
Set point regulation
Table 3: List of values for logbook
Note: A level set point is highly recommended.
Be aware of proper functioning of the AKS 4100 280 mm.
Heat pump application can only be provided if the mentioned recommendations are followed,
and the level set point in UniSAB III is set between 20 and 25%.
Filled in values
Mode d'emploi - ChillPAC et LP ChillPAC Mk 3
64/69
Annexes
Recommended
values
D22
NO
280 mm
210 mm
60 mm
See the list in Fig. 39
(heat pump: approx. 1.2–
1.4)
0 mm
1 sec.
150
0 mm
260 mm
100%
20% – 25%
010823 fr 06/2021