Electrical Installation - OEG 650 001 127 Notice De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

IMPORTANT:
Installation must be carried out by a qualified technician. This section is provided for
information purposes only and has to be checked and adapted if necessary according
to the actual installation conditions.
For safety reasons and to maintain the functional integrity of the electrical system,
the unit must be connected to the general power supply according to the following
regulations:
Upstream, the general power supply must be protected by a 30 mA differential switch.
The heat pump must be connected to a suitable D-curve circuit breaker (see table below)
in accordance with current national standards and regulations.
The power supply cable must be adapted to match the rated power of the unit
(see table below). The cable must be suitable for outdoor use.
For a three-phase system, it is essential to connect the phases in the correct sequence.
If the phases are inverted, the compressor of the heat pump will not work.
In places open to the public, it is mandatory to install an emergency stop button close
to the heat pump.
Models
Power supply
650 001 127
650 001 128
650 001 129
single phase
650 001 130
230~50 Hz
650 001 181
650 001 183
650 001 195
3-phase
650 001 199
380-415V/
650 000 200
3N~50 Hz
650 000 201
1
Cable cross-section suitable for max. cable length of 10 metres. For longer
than 10 metres, consult your electrician.
Swimming pool heat pump
Max. current (A)
Cable diameter
6.3
RO2V 3x2.5 mm²
8.3
RO2V 3x2.5 mm²
11.8
RO2V 3x4 mm²
13.4
RO2V 3x4 mm²
15.4
RO2V 3x4 mm²
17.2
RO2V 3x6 mm²
5.0
RO2V 5x2,5 mm²
9.4
RO2V 5x2,5 mm²
10.0
RO2V 5x2,5 mm²
12.8
RO2V 5x2,5 mm²

Electrical installation

Thermal-
magnetic
(D-curve)
protection
16A
16A
16A
20A
20A
20A
20A
20A
20A
20A
57
3.7
GB