Installation and Operating Instructions
UK
CHAPTER 3
COMMISSIONING
Temperature Control System WHS HE
2.7
Actuator 24V
The actuator is used for the motorised drive of the 3-way-valve. The angle of rotation is limited to 90°. When the end
stops are reached, the actuator is switched off electrically and currentless. In case of control system failures, the drive
can be switched to manual operation using an additional rotary encoder.
– Technical data
– Operating voltage:
– Electr. power consumption: 2.5 W
– Protection class:
– IP class:
– Torque:
– Run time (90°):
– Ambient temperature:
– Connecting cable length:
– Wiring diagram SS-954
03.12.09
3.0
Initial commissioning using electronic control unit WHSE
1. Check correct wiring.
2. If everything is attached correctly, connect the supply voltage and carry out the following tests for the respectively
correct temperature regulation.
– Function test
1. Set DIP switch 4 (Pos.) to position A and DIP switches 1, 2, 3 and 5 to position B.
2. Turn MIN pot (Pos.Ž) clockwise to the end position.
LED Y1 (Pos.) should flash and the actuator should open the 3-way-valve.
3. Turn MIN pot (Pos.Ž) anti-clockwise to the end position.
LED Y1 (Pos.) should flash and the actuator should close the 3-way-valve.
... in case of external setpoint pot (TFR):
4. Set DIP switches (Pos.) 3 and 5 to position A and DIP switches 1, 2 and 4 to position B.
5. Turn the external setpoint pot (TFR) clockwise to the end position.
LED Y1 (Pos.) should flash and the actuator should open the 3-way-valve.
6. Turn the external setpoint pot(TFR) anti-clockwise to the end position.
LED Y2 (Pos.‘) should flash and the actuator should close the 3-way-valve.
Œ

Ž
– After the test
Set the desired control mode via the Dip switches (Pos.) to the correct position (see SS-953).
For constant room temperature control with minimum limit, set the cascade factor CF (Pos.) and the MIN pot (Pos.Ž)
to the desired minimum supply air temperature.
For supply air temperature and constant room temperature control, CF (Pos.) should be set to 1 to ensure stable re-
gulation.
24V / 50/60 Hz
II (protective insulation)
IP 44
5 Nm
140 s
0 °C - +50 °C
2.2 m (with wire end ferrules)

Actuator

Stellantrieb
zu WHSH
to
24V~
~
~
24V~ 50/60Hz
Œ Setpoint temperature for operation with constant supply air temperature

‘
 CF = Cascade factor setting
Ž MIN = Minimum limit
 Setting/selection of control mode via Dip switches
 ctuator operating display Y1
‘ ctuator operating display Y2
’ nti-freeze: LED alarm and reset button
“ Operating display
10
Fig. 14