Télécharger Imprimer la page

Lutron LUT-LBX-CE Instructions D'installation page 5

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 8
P P a a n n e e l l M M o o u u n n t t i i n n g g
The enclosure must be in accordance with all local and national
electrical codes.
Lutron does not recommend using a door to enclose the front of
a panel, since this restricts airflow to the GRAFIK Eye Control
Units and Interfaces.
If mounting multiple Control Units or Interfaces in an enclosure:
1 1 . . Ambient temperature within an enclosure must remain
between 32 °F - 104 °F (0 °C - 40 °C).
2 2 . . If not mounting in a metal enclosure, all units m m u u s s t t be mount-
ed in a wallbox.
To improve heat dissipation of the Interface, remove the faceplate
from the unit.
GRAFIK Eye Control Units and Interface Units dissipate heat
when operating. Obstructing these units can cause mal-
function to both the Control Unit and the Interface if ambient
temperature does not remain between 32 °F - 104 °F
(0 °C - 40 °C).
T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g G G u u i i d d e e
S S y y m m p p t t o o m m
Lights do not come on.
Lights turn on/off
unexpectedly.
C C a a u u s s e e s s
Power is off
Miswire
Bulb(s)/lamp(s) burned out
Control Unit
Load Type
Miswire
Control Unit
Damaged/disconnected
LUT-LBX-CE
PB
4 1/2 in. (115 mm) minimum
4 1/2 in. (115 mm) minimum
LUT-
LBX-CE
S S o o l l u u t t i i o o n n
Restore power to the control unit.
Confirm wiring per wiring diagrams.
Replace bulb(s)/lamp(s).
Refer to troubleshooting section of Control Unit
Installation Guide.
Confirm that the load type being switched/dimmed is
compatible with the control unit or dimmer being used.
Line/Mains voltage phase control dimming only.
Confirm wiring per wiring diagrams.
Refer to the troubleshooting section of Control Unit
Installation Guide.
Lighting load does not meet minimum requirements of
dimmer; check for damage or disconnection.
5 5
ELVI

Publicité

loading