Extension module KWL-EM eC for easyControls
5�3 Warm water post-heating
WW post-heating with WHSH HE 24V (0-10V)
5�3�1 Components required for installation
– Ventilation unit with easyControls 3.0 control system
– WHR 125 or WHR 160
– WHSH HE 24V (0-10V)
– 1 x KWL-EM eC
– 2 x KWL-LTK eC
5�3�2 Setup via web interface
1. Select the menu item Configuration on the web interface and Heating settings in the
submenu.
2. Select Auxiliary heating, Warm water post-heating.
The max� outdoor temperature setting defines the max� outdoor temperature up to
which the post-heating is active�
3. The desired supply air temperature can now be individually set on the homepage in
the ventilation profiles.
5�3�3 Setup via the KWL-BE Touch controller
1. Select the menu item Configuration
2. Select Auxiliary heating, Warm water post-heating.
The max� outdoor temperature setting defines the max� outdoor temperature up to
which the post-heating is active�
3. The desired supply air temperature can now be individually set on the homepage in
the ventilation profiles.
and Heating settings
7
EN
in the submenu.