MONTAGE- UND BETRIEBSVORSCHRIFT
INSTALLATION AND OPERATING INSTRUCTIONS
NOTICE DE MONTAGE ET D'UTILISATION
KNX/EIB-Modul
KNX/EIB module
Module KNX/EIB
KWL-KNX
Zum Anschluss eines KWL-Lüftungsgerätes
an ein KNX/EIB-Gebäudeleitsystem
For the connection of the KWL ventilation unit
to a KNX/EIB central building control system
Pour le raccordement d'une centrale KWL
au système domotique KNX/EIB
DE
EN
FR

Publicité

Table des Matières
loading

Sommaire des Matières pour Helios KWL-KNX

  • Page 1 Helios Ventilatoren MONTAGE- UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS NOTICE DE MONTAGE ET D’UTILISATION KNX/EIB-Modul KNX/EIB module Module KNX/EIB KWL-KNX Zum Anschluss eines KWL-Lüftungsgerätes an ein KNX/EIB-Gebäudeleitsystem For the connection of the KWL ventilation unit to a KNX/EIB central building control system Pour le raccordement d’une centrale KWL...
  • Page 2: Table Des Matières

    DEUTSCH Helios Ventilatoren MONTAGE- UND BETRIEBSVORSCHRIFT Inhaltsverzeichnis KAPITEL 1 ALLGEMEINE MONTAGE- UND BETRIEBSHINWEISE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Seite 1 Wichtige Informationen .
  • Page 3: Wichtige Informationen

    Wenn die nachfolgenden Ausführungen nicht beachtet werden, entfällt unsere Gewährleistung. Gleiches gilt für Haftungsansprüche an den Hersteller. Der Gebrauch von Zubehörteilen, die nicht von Helios empfohlen oder angeboten werden, ist nicht statthaft. Even tuell auftretende Schäden unterliegen nicht der Gewährleistung.
  • Page 4: Emv-Anforderungen

    Erfüllt EMV Richtlinie 2004/108/EG; EN 50090-2-2 und EN 50491-5-2 1 .9 Allgemeines Helios Lüftungsgeräte KWL EC... können mittels Zusatzmodul KWL-KNX (einem EIB-RS485 Gateway) an einen KNX-Bus angeschlossen werden (s.a. Schaltplan SS-1076). Mit dem KWL-KNX erhält man vom Lüftungsgerät Zustandsdaten wie z.B. den Status der Ventilatoren oder auch Ablesewerte von z.B. Temperaturfühlern und Kohlendioxid-Fühlern.
  • Page 5: Programmierung Über Ets-Software

    Das KWL EC-Lüftungsgerät muss mindestens Softwareversion 2 .03 haben . WICHTIG Ein Upgrade erfolgt über das Helios-Steuerungskonzept easyControls (siehe Anleitung Nr. 82237: Einregulie- rung und Inbetriebnahme – easyControls). Über die Webbrowseroberfläche im Menü „Erstinbetriebnahme” den Button „Software jetzt aktualisieren”...
  • Page 6: Gruppenobjekte

    Montage- und Betriebsvorschrift KNX/EIB-Modul KWL-KNX 2 .3 Gruppenobjekte Nr . Name Funktion Lenght Direction Lüftungsgerät - Lüfterstufe Soll Stellwert DPST-5-10 1 Byte Lüftungsgerät - Lüfterstufe Ist Statuswert DPST-5-10 1 Byte Lüftungsgerät - Lüfterstufe Soll Prozentwert DPST-5-1 1 Byte Lüftungsgerät - Lüfterstufe Ist...
  • Page 7: Parameter

    Montage- und Betriebsvorschrift KNX/EIB-Modul KWL-KNX Nr . Name Funktion Lenght Direction 59 Externer Fühler - Relative Feuchte 1 Statuswert DPST-9-7 2 Bytes OUT 60 Externer Fühler - Relative Feuchte 2 Statuswert DPST-9-7 2 Bytes OUT 61 Externer Fühler - Relative Feuchte 3...
  • Page 8: Register

    Montage- und Betriebsvorschrift KNX/EIB-Modul KWL-KNX 2 .5 Register Gruppenobjekte Struktur Variablen Anmerkung Nr . Name Nr . Name Name Lüftungsgerät - Lüfterstufe Soll T_BTSystemPar uint16_t u16NewFanLevelFromLt Bit 5...Bit 0 = nValueGo Lüftungsgerät - Lüfterstufe Ist T_BTSystemPar uint16_t u16NewFanLevelFromLt nValueGo = Bit 5...Bit 0 Lüftungsgerät - Lüfterstufe Soll...
  • Page 9 Montage- und Betriebsvorschrift KNX/EIB-Modul KWL-KNX Gruppenobjekte Struktur Variablen Anmerkung Nr . Name Nr . Name Name 51 Externer Fühler - Temperatur 1 32 T_ExtSensorTEMP float ValueTEMP[0] 52 Externer Fühler - Temperatur 2 32 T_ExtSensorTEMP float ValueTEMP[1] 53 Externer Fühler - Temperatur 3...
  • Page 10 ENGLISH Helios Ventilatoren INSTALLATION AND OPERATING INSTRUCTIONS Table of Contents CHAPTER 1 . GENERAL INSTALLATION AND OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1 Important information .
  • Page 11: Important Information

    Our warranty shall not apply if the following instructions are not observed. The same applies for liability claims against the manufacturer. The use of accessories, which are not recommended or offered by Helios, is not permitted. Any damage that may occur is not liable for warranty.
  • Page 12: Emc Requirements

    2 .0 Installation/assembly CHAPTER 2 The KWL-KNX is intended for top hat rail mounting in the switch cabinet. E.g. a JY(ST)Y 2x2x0.6 mm² + 0.5 mm² cable is used for the cabling between the KWL ventilation unit and module. INSTALLATION/ ASSEMBLY 2 .1...
  • Page 13: Programming Via Ets Software

    The KWL EC ventilation unit must have software version 2 .03 as a minimum . IMPORTANT Upgrading takes place via the Helios control concept easyControls (see instructions no. 82237: Adjustment and starting up – easyControls). Using the web browser interface, press the button “Upgrade software now” in the “Initial Commissioning”...
  • Page 14: Group Objects

    Installation and Operating Instructions KNX/EIB Module KWL-KNX 2 .3 Group objects No . Name Function Length Direction Ventilation unit - Fan stage Target Setpoint DPST-5-10 1 Byte Ventilation unit - Fan stage Actual Status value DPST-5-10 1 Byte Ventilation unit - Fan stage Target...
  • Page 15: Parameters

    Installation and Operating Instructions KNX/EIB Module KWL-KNX No . Name Function Length Direction 59 External sensor - Relative humidity 1 Status value DPST-9-7 2 Bytes OUT 60 External sensor - Relative humidity 2 Status value DPST-9-7 2 Bytes OUT 61 External sensor - Relative humidity 3...
  • Page 16: Register

    Installation and Operating Instructions KNX/EIB Module KWL-KNX 2 .5 Register Group objects Structure Variables Comment No . Name No . Name Type Name Ventilation unit - Fan stage Target T_BTSystemPar uint16_t u16NewFanLevelFromLt Bit 5...Bit 0 = nValueGo Ventilation unit - Fan stage Actual...
  • Page 17 Installation and Operating Instructions KNX/EIB Module KWL-KNX Group objects Structure Variables Comment No . Name No . Name Type Name 51 External sensor - Temperature 1 32 T_ExtSensorTEMP float ValueTEMP[0] 52 External sensor - Temperature 2 32 T_ExtSensorTEMP float ValueTEMP[1]...
  • Page 18 FRANÇAIS Helios Ventilateurs NOTICE DE MONTAGE ET D’UTILISATION Sommaire CHAPITRE 1 . INFORMATIONS GÉNÉRALES DE MONTAGE ET D’UTILISATION . . . . . . . . . . . . . . . . . . . . . . . Page 1 Informations importantes .
  • Page 19: Chapitre 1 . Informations Générales De Montage Et D'utilisation

    Toute demande de remplacement ou de réparation à titre gratuit sera déclinée en cas de non-respect des indications contenues dans la notice. L’utilisation d’accessoires, non fournis, non conseillés ou non proposés par Helios, est interdite. Si ces consignes ne sont pas respectées, la garantie s’annule. Idem pour les réserves constructeur.
  • Page 20: Exigences Emv

    CHAPITRE 2 2 .0 Installation/Montage INSTALLATION/MON- Le KWL-KNX est conçu pour un montage sur rail en armoire. Le raccordement entre la centrale KWL et le TAGE module peut se faire avec un câble JY(ST)Y 2x2x0.6 mm² + 0.5 mm². 2 .1 Raccordement électrique...
  • Page 21: Programmation Via Logiciel Ets

    L’appareil KWL EC doit disposer de la version de logiciel version 2 .03 ou postérieure . IMPORTANT Une mise à jour est disponible via la commande Helios easyControls (voir la notice N° 82237: Paramétrage et mise en service - easyControls).
  • Page 22: Groupes Objets

    Notice de montage et d’utilisation Module KNX/EIB KWL-KNX 2 .3 Groupes d’objets N° Désignation Fonction Long . Direction Groupe VMC - Vitesse ventilateur - Consigne Valeur de réglage DPST-5-10 1 Byte Groupe VMC - Vitesse ventilateur - Effective Valeur du statut...
  • Page 23: Paramètres

    Notice de montage et d’utilisation Module KNX/EIB KWL-KNX N° Désignation Fonction Long . Direction 59 Sonde externe - Humidité relative 1 Valeur du statut DPST-5-10 2 Bytes OUT 60 Sonde externe - Humidité relative 2 Valeur du statut DPST-5-10 2 Bytes OUT 61 Sonde externe - Humidité...
  • Page 24: Registre

    Notice de montage et d’utilisation Module KNX/EIB KWL-KNX 2 .5 Registre Groupes d’objets Structure Variables Remarque N° Désignation N° Désignation Type Désignation Groupe VMC - Vitesse ventilateur - Consigne T_BTSystemPar uint16_t u16NewFanLevelFromLt Bit 5...Bit 0 = nValueGo Groupe VMC - Vitesse ventilateur - Effective...
  • Page 25 Notice de montage et d’utilisation Module KNX/EIB KWL-KNX Groupes d’objets Structure Variables Remarque N° Désignation N° Désignation Type Désignation 51 Sonde externe - Température 1 32 T_ExtSensorTEMP float ValueTEMP[0] 52 Sonde externe - Température 2 32 T_ExtSensorTEMP float ValueTEMP[1] 53 Sonde externe - Température 3...
  • Page 26 Montage- und Betriebsvorschrift KNX/EIB-Modul KWL-KNX...
  • Page 27 Montage- und Betriebsvorschrift KNX/EIB-Modul KWL-KNX...
  • Page 28 HELIOS Ventilatoren GmbH + Co KG · Lupfenstraße 8 · 78056 VS-Schwenningen HELIOS Ventilateurs · Le Carré des Aviateurs · 157 avenue Charles Floquet · 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG · Tannstraße 4 · 8112 Otelfingen GB HELIOS Ventilation Systems Ltd.