MODE3 CONFIG
HELP SET:OFF
MODE3 CONFIG
HELP TIME:5m
Configuring MODE 4
SELECT
MODE CONFIG
9
MODE CONFIG
MODE:1
6
9
9
MODE CONFIG
SETUP
9
• Enable (ON) or disable (OFF) activation of the second electric pump (safety)
• This parameter is used to enable the second electric pump with a program-
mable time (even if there is no second input IN2)
• Safety electric pump activation time
Default 5 min
MODE:4
MODE4 CONFIG
IN1:ON
MODE4 CONFIG
IN2:ON
MODE4 CONFIG
LOGIC:ALTERN.
MODE4 CONFIG
HELP SET:OFF
MODE4 CONFIG
HELP TIME:5m
Range 0-60 min
• Press the
key to confirm the choice and enter the submenu.
• Press the
key to enter the submenu and change mode.
• Press the
or
key to select mode 4
(from modes 1 to 6)
• Press the
key to confirm the choice of MODE:4
• Press the
key to continue with the configuration
• Press the
key to enter the mode 4 configuration submenu
• Enable (ON) or disable (OFF) input IN1
• This input is used to start a single electric pump according to the al-
ternating logic
• Enable (ON) or disable (OFF) input IN2
• This input is used to start the second electric pump according to the
alternating logic, or to start both electric pumps simultaneously
• If the system has two electric pumps, enable (ALTERN.) or disable
(SINGLE) the alternating logic.
• Enable (ON) or disable (OFF) activation of the second electric pump
(safety)
• This parameter is used to enable the second electric pump with a pro-
grammable time (even if there is no second input IN2)
• Safety electric pump activation time
Default 5 min
Step 1 min
Range 0-60 min
Step 1 min