PUMP1 CONFIG
VOLT MIN
PUMP1 CONFIG
VOLT MAX
PUMP1 CONFIG
VOLT TOUT
PUMP1 CONFIG
COSFI MIN:0.50
PUMP1 CONFIG
COSFI TOUT:5s
PUMP1 CONFIG
CURR MIN
PUMP1 CONFIG
CURM TOUT
PUMP1 CONFIG
MOT PROT:OFF
PUMP1 CONFIG
DISABLE:OFF
If there is an electric pump no. 2
Use the same procedure to configure electric pump no. 2
• Set the minimum permissible voltage for correct control panel operation.
• If voltage (read) < voltage (set minimum), the control panel enters the MIN VOLTAGE
alarm state.
Default 0 V
• Set the maximum permissible voltage for correct control panel operation.
• If voltage (read) < voltage (set maximum), the control panel enters the MAX VOLTAGE
alarm state.
Default 460 V
• Set the overvoltage or undervoltage trip delay time.
Default 5 sec
• Set the minimum permissible cosφ to protect the electric pump from dry running
(from the rating plate or measured).
• If the read cosφ is less than the set minimum cosφ, the control panel enters an alarm
state.
Default 0.5
• Set the dry running trip delay time.
Default 5 sec
• Set the minimum permissible current to protect the electric pump from dry running
(from the rating plate or measured).
• If current (read) < current (set minimum), the control panel enters an alarm state due
to DRY RUNNING.
Default 5.0 A
• Set the trip delay time for dry running due to minimum current.
Default 5 sec
• Enable or disable motor protection by the thermal cut-outs connected to inputs T1
and T2 (klicson).
Default OFF
• Enable or disable electric pump operation when it is under maintenance or has failed.
Default OFF
PUMP2 CONFIG
Range 0–460 V
Range 0–460 V
Range 0–20 sec
Range 0–1
Range 0–20 sec
Range 0–18 A
Range 0–20 sec
Range OFF–ON
Range OFF–ON
SELECT
Step 1 V
Step 1 V
Step 1 sec
Step 0.01
Step 1 sec
Step 0.1
Step 1 sec
Step /
Step /