This document contains installation instructions
for the Eve Single. Please always refer to our
website for the most up-to-date and complete
manual for the product.
www.alfen.com/en/downloads
Installation conditions
The installation must comply with standards
and (local) regulations and must only be carried
out by a qualified technician.
Conditions of use
Operating temperature
Relative humidity
Electrical safety class
Protection rating
Mechanical impact
Nominal input voltage
Single-phase
230 V ± 10%
3-phase
400 V ± 10%
Short-circuit protection (system circuit breaker)
Single-phase
1x 20A, 1P,
16 A
char. B or C
1x 40A, 1P,
32 A
char. B or C
Short-circuit protection (cartridge fuses)
Single-phase
16 A
1x 20A gG
32 A
1x 35A gG
Residual current device
Single-phase
16 A
Type B, 30 mA, 20A
32 A
Type B, 30 mA, 40A
Earthing
TN system
PE cable
self-installed earth electrode,
TT system
< 100 Ohm earth dispersion
resistance
Minimum power supply cable diameters
(for max. length of 50 m)
Single-phase
16 A
4 mm
32 A
6 mm
en
-25 °C /+40 °C
5% / 95%
I
IP55
IK10
50 Hz
50 Hz
3-phase
1x 20A, 3P,
char. B or C
1x 40A, 3P,
char. B or C
3-phase
3x 20A gG
3x 35A gG
3-phase
3-phase
2
2
4 mm
2
2
6 mm
6
5
8
1
4
E-Socket cable
power cable
ethernet cable
1
2
3
4 5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
PE L3 L2 L1 N
PE L3 L2 L1 N
2
3
5
6
7
7