EcoSystem Power Module / Junction Box Mount | Install Guide
Installation
Step 1: Determining Mounting Location
for Module
• EcoSystem Power Modules must be mounted onto
a 4 in x 4 in (102 mm x 102 mm) standard (1900)
junction box (not included, but available: Lutron P/N
241296). Follow applicable local and national codes.
NOTE: The wire length between the dimming module
and the ballast it is controlling shall not exceed 500 ft
(152 m).
• Mount the module indoors with ambient temperature
between 32 °F and 104 °F (0 °C and 40 °C) and
humidity < 90% (non-condensing).
Shock Hazard. May result in serious injury or death.
WARNING
Turn off power at circuit breaker before installing the unit.
DO NOT INSTALL WHILE ENERGIZED. Do not
Gevaar voor elektrische schokken. Gevaar voor ernstig
WAARSCHUWING
connect any electrically live circuits to the module
of fataal letsel. Schakel voor de installatie van de
eenheid met de hoofdschakelaar de stroom uit.
prior to installation.
Peligro de descargas eléctricas. Puede causar lesiones
5 in
PRECAUCIÓN
graves o letales. Corte el suministro eléctrico en
(130 mm)
el magnetotérmico antes de instalar la unidad.
Perigo de choque. Pode provocar graves lesões ou morte.
AVISO
Desligue a alimentação no disjuntor antes de instalar a unidade.
Risque de choc. Peut entraîner de graves blessures
AVERTISSEMENT
ou la mort. Couper l'alimentation au niveau
du disjoncteur avant d'installer l'appareil.
Lebensgefahr. Gefahr schwerer oder tödlicher Verletzungen.
ACHTUNG
Vor Installation des Geräts den Strom am Sicherungs-
automaten abstellen.
电击危险。可导致死亡或严重受伤事故。在安装设备之前
警告
必须断开断路器处电源。
警告
Ceiling
電擊危險。可導致死亡或嚴重受傷事故。在安裝設備之前必
須斷開斷路器處電源。
EcoSystem Power Module Wiring
Distribution
Panel
Ground
Neutral
Live
www.lutron.com /support
2.5 in
(64 mm)
7.8 in
(150 mm)
.
.
,
.
The module can be
mounted on vertical
or horizontal surfaces
(e.g. ceiling). Mount in a
location where the PWR
and STAT indicators are
Wall
visable.
(See additional ballast installation guides for wire and terminal requirements)
Green
White
Black
Orange (Dimmed Hot): C5-BMJ-16A
Note: Colors indicated are
for wires coming out of
the module
CLASS 2 LOW VOLTAGE WIRING
Step 2: Wiring Power Module to
Mains and Loads
Live and neutral from a distribution panel is required
to power the module.
Lighting loads must match the selected input
voltage. Verify that 120 V~ loads are used only with
120 V~ mains, and 277 V~ loads are used only
with 277 V~ mains. DO NOT use different voltage
loads on the same control circuit.
Dimming Power Module
Three wires are used between the BMJ module
and a Hi-lume or Eco-10 ballast. The wires are
color-coded as follows:
C5-BMJ-16A Ballast
Red
Orange
White
Green
Switching Power Module
Two wires are used between the XPJ and non-dim
loads. The wires are color coded as follows:
C5-XPJ-16A Load
Red
White
Green
Module can support up to 16 A of attached switched
load current.
Use the following steps to wire a module to mains
and ballast(s):
A. DO NOT WIRE LIVE. Interrupt power via breaker
before wiring between the module and a ballast.
B. Connect mains feed wires and output wires to the
Power Module as shown in the diagram below.
Green (Ground)
White (Neutral)
Red (Switched Hot)
To Additional Loads
2
Black
Switched Hot
Orange Dimmed Hot
White
Neutral
Green
Ground
Black
Switched Hot
White
Neutral
Green
Ground
Fixture Ground
Green
White
Black
Lutron FDB or
ECO Dimming Ballast
Orange
Fixture Ground
Green
White
Black
Non-Dim Load
®