ATTENTION: Please read this guide before installing
EcoSystem Dimming Power Module: C5-BMJ-16A
EcoSystem Switching Power Module: C5-XPJ-16A
EcoSystem Power Module for control of Lutron
3-wire dimming ballasts and non-dim loads.
4 in. x 4 in. Junction Box
~
27 7
V
10 0–
Ma x.
16 A
O N
O N
LU TR
LU TR
R
ICA TO
R IND
it has
PO WE
n un
Ca utio
On :
r
po we
g
ctio nin
Off : is no t fun
rly
pro pe
gh t
gh t
Da yli
Da yli
Se ns
or
EcoSystem
Bus
Front Cover
Overview
•
A C5-BMJ-16 Module converts a circuit of one or more
Lutron Eco-10
/Hi-lume
TM
EcoSystem component.
•
A C5-XPJ-16 Module converts a circuit of non-dim loads
into an EcoSystem component.
•
The module connects directly to the EcoSystem Bus and
accepts an occupant sensor, daylight sensor and infrared
wallstation control inputs to drive the attached dimming
ballast(s).
EcoSystem Bus
EcoSystem
Ballast
IR Receiver
* not counted as one of the 64 devices allowed on the EcoSystem bus
Technical Support: 1-800-523-9466
Hz
50 /60
Class 2
Wiring
Input
dimming ballast into an
®
EcoSystem
EcoSystem Module
Bus Supply*
Occupant
sensor
Lighting
Remote
24 hours/7 days
Specifications
EcoSystem Power Modules control up to 16 A of
Lutron 3-wire dimming ballasts (Hi-lume and Eco-10
only) or non-dim loads, and have the following
characteristics:
•
Input voltage 100 - 277 V~
•
Maximum switched load: 16 A
•
Provides switching output and dimming control
(BMJ only)
•
Power Module power draw: 2 VA
•
Dimming Power Module provides continuous dimming
throughout the ballasts specified range
• 500 feet (152 m) maximum wire length between
BMJ and controlled dimming ballast
•
Single address on the EcoSystem Bus
•
Accepts up to three sensors, one each of the following
types:
1.
2.
3.
N N O O T T E E : : It is possible to connect more than 1 ballast
or load to a module. The module controls up to 16 A
of connected load as a single zone. I I f f m m o o r r e e t t h h a a n n o o n n e e
l l o o a a d d i i s s a a t t t t a a c c h h e e d d , , t t h h e e l l o o a a d d s s c c a a n n n n o o t t b b e e c c o o n n t t r r o o l l l l e e d d
i i n n d d e e p p e e n n d d e e n n t t l l y y . .
B B M M J J / /
X X P P J J
Eco-10 or
Hi-lume ballast(s)
Daylight Sensor
Occupant Sensor
Infrared Receiver or Wallstation
Up to 64
devices total
EcoSystem
Ballast
Daylight Sensor
Wallstation
Lutron
EcoSystem
Ballast
| 1
®