Addr
Description
4241
Factor for the minimum
voltage of the lineariza-
tion point with respect to
the nominal voltage in
combined controller mode
(parameter for the statics
controller).
4242
Max. time between signal
high and closed AC-con-
tactor
4280
Sets the output power to
S = 0 kVA. Only availa-
ble for some grid code
functions.
4281
maximum P, controllable
by VNB via ModBus.
100 % is equivalent to
Smax * OLC (e.G. 25000
* 1,5 = 37500)
4282
Activates a startup ramp.
Only available for some
grid code functions.
4300
Configuration DC stage:
0 = DC module is off,
power electronic circuit is
deactivated, battery vol-
tage can be measured.
1 = DC module is active
(DC link voltage control)
2 = DC module is active
(current source mode or
in DC droop mode)
5000
State of device: PowerUP
-> 0, Error -> 1, Idle ->
2, Operation -> 3, Mainte-
nance -> 4
5001
Number of connected
slave modules
5002
Number of connected
sub slave modules
5020
Nominal grid frequency
5021
Nominal grid voltage
5022
Nominal apparent power
capability
76
Manipulation
Unit
Res
Default
olu-
tion
%
1.0
90
ms
1.0
100
-
1.0
0
W
0.01
15000
-
1.0
0
-
1.0
1
-
1.0
-1
cnt
1.0
0
cnt
1.0
0
Hz
0.1
500
V
1.0
400
VA
1.0
25000
Min
Max
Dat
Typ
atyp
e
e
75
110
UIN
Regi
T16
ster
0
100
UIN
Regi
00
T16
ster
0
1
UIN
Regi
T16
ster
0
200
UIN
Regi
00
T16
ster
0
1
UIN
Regi
T16
ster
0
2
UIN
Regi
T16
ster
-2
10
INT
Regi
16
ster
16
UIN
Regi
T16
ster
0
5
UIN
Regi
T16
ster
UIN
Regi
T16
ster
UIN
Regi
T16
ster
UIN
Regi
T16
ster
2022-03-23
Len
FCr
FCw
gth
1
03
06
1
03
06
1
03
06
1
03
06
1
03
06
1
03
06
1
04
1
04
1
04
1
04
1
04
1
04
A67-0141-00.BKfr-0
01-09