Number
Message
50049
Overvoltage L3
RMS.
50050
Undervoltage L1
RMS.
50051
Undervoltage L2
RMS.
50052
Undervoltage L3
RMS.
50053
Grid contactor
could not be closed.
50068
Subslave communi-
cation alarm.
50069
Master communica-
tion alarm.
50080
Overvoltage grid N
to PE.
50081
Overvoltage internal
DC link.
50082
Overvoltage internal
N to PE.
50083
Overvoltage exter-
nal DC link positive
part.
50084
Overvoltage exter-
nal DC link nega-
tive part.
50085
Overvoltage exter-
nal DC link.
50086
Overvoltage exter-
nal DC link mid-
point to PE.
50087
Wrong polarity on
DC link detected.
50088
Overvoltage exter-
nal 24-V auxiliary
supply.
50089
Undervoltage exter-
nal 24-V auxiliary
supply.
50095
AC-DC module
hardware protection
alarm.
50096
DC link precharge
unit alarm.
A67-0141-00.BKfr-0
01-09
Effect
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
No operation pos-
sible.
2022-03-23
Cause
Action
Overvoltage L3
Check grid settings,
RMS.
grid voltage L3 and
external devices.
Undervoltage L1
Check grid settings,
RMS.
grid voltage L1 and
external devices.
Undervoltage L2
Check grid settings,
RMS.
grid voltage L2 and
external devices.
Undervoltage L3
Check grid settings,
RMS.
grid voltage L3 and
external devices.
Grid contactor
Check the contac-
could not be closed.
tor, delaytime, cabl-
ing, AUX-suppy of
contactor etc.
Subslave communi-
Check cabling to
cation alarm.
subslaves and sys-
tem start-up routine.
Master communica-
Check cabling to
tion alarm.
master and system
start-up routine.
Overvoltage grid N
Check voltage N to
to PE.
PE, N and PE con-
nections.
Overvoltage internal
Contact service.
DC link.
Overvoltage internal
Contact service.
N to PE.
Overvoltage exter-
Check DC link vol-
nal DC link positive
tage and midpoint.
part.
Overvoltage exter-
Check DC link vol-
nal DC link nega-
tage and midpoint.
tive part.
Overvoltage exter-
Check DC link vol-
nal DC link nega-
tage and midpoint.
tive part.
DC link is unsyme-
Check DC link vol-
tric.
tage and midpoint.
Wrong polarity on
Check DC link pola-
DC link detected.
rity.
Overvoltage exter-
Check the external
nal 24-V auxiliary
24-V auxiliary sup-
supply.
ply.
Undervoltage exter-
Check the external
nal 24-V auxiliary
24-V auxiliary sup-
supply.
ply.
AC-DC module
Check for other
hardware protection
error messages.
alarm.
Precharge unit fai-
Contact service.
led.
Recherche des erreurs
Detec-
ted by
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module