6.3.2 UCS900 UNIT
1
•
All quotes for fixing and connecting the unit to the system are shown in Enclosure
5/A and 5/B;
2
•
Take the 4 brackets and screws from the carton box and fix them to the metal struc-
ture of the unit;
•
If the unit has a fresh air and/or supply duct, please proceed as indicated in Para-
3
graph 6.9;
•
We suggest to install to the structural ceiling 4 corrugated steel bars (diam. 8 mm),
with proper nuts and length related to the correct positioning of the unit on the false
4
ceiling;
•
Lift the unit and hook the brackets to the 4 steel bars, as shown in Fig.6;
•
Verify that the unit is in horizontal position. In case of adjustments, please act on the
5
regulating nuts (Fig.7) and make sure that at the end the unit is well fixed;
•
Connect the unit to the hydraulic system as described in Paragraph 6.5;
6
7
8
9
Fig.6
10
•
Connect the water condensate discharge pipe by following the indications of Para-
graph 6.6;
+
•
If foreseen, connect the air inlet and/or outlet ducts and make sure to use also a
thermal and acoustic insulation, in order to avoid dispersions and/or water condens-
ing problems;
•
Connect the unit electrically by following the instructions given on Paragraph 6.8;
•
Fix the supply grilles by the four M6 pivots and lock them with the 4 self-locking nuts
M6 contained in the accessories box (Fig.8 and Fig.9);
•
Insert and fix the air filter inside the support in the frame corners (Fig.10);
•
Clamp the air suction grill by inserting the hooks in the dedicated slots;
•
Clamp the black safety rope to the hole in the frame (Fig.10);
38
41
Fig.7