Fnr Type of fault
Short circuit measuring element 1
52
(NTC).
Temperature of the probe above
53
the operating temperature range
(-32°C...170°C).
Temperature of the probe below
54
the operating temperature range
(-32°C...170°C).
59 Both sensor elements faulty.
Interruption measuring element 2
61
(Pt 1000).
Short circuit measuring element 2
62
(Pt 1000).
Detected sensor drift
71
exceeds warning level.
Detected sensor drift
72
exceeds alarm level.
Supply voltage outside the
91
operating voltage range.
Operating temperature of the
92
electronics outside the specified
range.
1)
Setting of parameter drEd: "On" or "Ondr".
24
Corrective measures
Replace the unit.
(Sensor backup is possible).
Reduce medium temperature.
Increase medium temperature.
Replace the unit.
Replace the unit.
(Sensor backup is possible).
Replace the unit.
(Sensor backup is possible).
First indication of drift detected,
prepare replacement of the unit.
Check if the parameter drW is
programmed correctly.
Drift exceeds alarm threshold,
replace the unit, temperature
measurement with reduced
accuracy possible.
Check if the parameter drA is
programmed correctly.
Check the supply voltage, provide
the indicated voltage.
Check the temperature of the
sensor top; ensure that the speci-
fied range is observed.
1)
1)
1)