W20L120 NOC
Rated light output in emergency
operation mode: 350lm
Polar intensi !Y diagram
120
°
180
120
°
°
60
30
°
(cdllOOO Im)
0
°
L.O.R.=
1.00
--0-180
°
--90-270
°
Charge time
Lifetime
The batteries have a life time expectancy of 4 years when maintained properly. Replace after that time!
Automatic emergency time selection
After installation and power up the driver will detect the battery and start the automatic detection process.
- During automatic detection, the indicator LED willlight up with short green flashes.
- Between minimum 6 and maximum 30 seconds the TrustSight driver will set the battery type (number of cells)
and will set the emergency output power accordingly.
After that, the system is defined and fully operational. The battery type definition has influence on the performance
during the self-test and on the battery charge method. When the automatic battery detection process is disrupted,
e.g. by switching off the permanent mains, the detection process is stopped and the TrustSight emergency driver
will go into emergency mode with the lowest output power. At a next power up, the automatic detection process
will start again.
Periodic testing
Periodic tests of emergency lighting luminaires must be performed according to EN50172 clause 7.2.3 and 7.2.4.
Switch on in the emergency mode each month by simulation of a failure of the supply to the normal lighting for
a period sufficient to ensure that each lamp is illuminated. Twice per year, each luminaire shall be tested for its
full rated duration (at least 3hrs).
For more information please consult the TrustSight Gen 3 Design in guide. The latest version is available online.
LED indicator status
LED indicator (color I flashing)
Green I no flashing
Off
Green I slow (0.25s on, 1.2Ss off)
Green I fast (0.25s on, 0.25s off)
Red I no flashing
Red I fast (0.25s on, 0.25s off)
Red I slow (0.25s on, 1.25s off)
Red-green I fast
Fast flashing: (on-time = 0.25s, off-time = 0.25s)
Slow flashing: (on-time = 0.25s, off-time = 1.25s)
Green I short
on-time = 50ms off-time = 0.95sl
W20L150 NOC
Rated light output in emergency Rated light output in emergency Rated light output in emergency
operation mode: 350lm
Polar intensi !}' diagram
°
°
180
120
120
°
(cd/1000 Im)
0
L.O.R.=
1.00
°
°
-0--180
-90--270
24.00
-�►
Error condition
Battery voltage too high or too low
Output voltage too low or too high
No load connected or output shorted
Failed test due to batte,y
W20L120OC
operation mode: 350lm
°
(cd/1000
Im)
0
L.O.R.=
1.00
-0--180
°
-90--270
Cause
System OK, batte,y fully charged
Mains off, EM mode, Rest mode, test in progress
System OK, batte,y is charging
System OK, recently tested ( < 5 days, Australia mode only)
No battery connected
Wrong or bad batte,y connected
Wrong LED load connected
Wrong connection
Batte,y end of life
Charger failure
DALI device identification
Batte,y detection
5/12
W20L150 OC
operation mode: 350lm
°
{cd/1000 Im)
0
L.O.R.= 1.00
°
--0--180
°
--90--270
Solution
I
Connect battery
Replace battery
Connect right load and pelform functional test
Connect right load and pelform functional test
Replace battery and pelform duration test.
Replace driver
°