The Pentair Pentek Solar Drive controller can operate 230V three phase or 230V single
phase three wire motors. In order for the Pentair Pentek Solar Drive to match the motor
specifications, the first three DIP switches on the left are used for motor selection (see
Figure 9).
DIP Switch 1 – 120/230Vac: If switched ON (up),
the unit is configured for 120Vac pump operation;
if switched OFF (down), the unit is configured for
230Vac.
DIP Switch 2 – 1/3 phase: If switched ON (up),
the unit is configured for single-phase motor
operation; if switched OFF (down), the unit is
configured for three-phase motor operation.
DIP Switch 3 – 50/60Hz: If switched ON (up),
the unit is configured for 50Hz motors; if switched
OFF (down), the unit is configured for 60Hz motors.
DIP Switches 4 and 5 – Minimum Operating Motor
Frequency: It is possible to set up a minimum
operating motor frequency. This is important when
operating in Solar Only mode and when there is not
enough solar power available to pump water due to
high dynamic head. In order to prevent "dead heading,"
it is possible to set the minimum frequency in the
range of 30 to 45Hz, using a combination of DIP
switches 4 and 5 as shown in Figure 10.
NOTE: The Pentair Pentek Solar Drive's default
minimum Hz setting is 30Hz.
DIP Switches 6 and 7 – Over-current Protection:
The Pentair Pentek Solar Drive can set over-current protection based on the motor
pump and controller combination being used. Figure 11 shows how to set up over-current
protection using DIP switches 6 and 7. The default value of RMS current (when both
switches are OFF) is 10A for single phase, and 8A for three phase. DIP switches 6 and 7 are
to be used to match or exceed the motor nameplate's SFAMPS in order to protect from
over-current.
For example, if a single phase motor has SFAMPS: 7.4A then DIP switches 6 and 7 have
to be set for 8A, as this is the next highest protection current for this motor. Configuring
over-current protection also configures automatic Dry Well Protection. The Pentair
Pentek Solar Drive monitors motor amperage for dry well protection, and no other dry well
sensor input is needed unless desired.
P1063 (10-03-19)
Solar Drive DIP Switch Settings
*
1
2 3 4 5 6 7 8 9 10 11 12
Figure 11: Over-current Protection
(Continued to next page)
1
2 3 4 5 6 7 8 9 10 11 12
Single Phase
120Vac
1
2 3
230Vac
Three Phase
Figure 9: DIP Switches
DIP Switches
Minimum Motor
4 and 5
Frequency
4
5
4
5
4
5
4
5
Figure 10: Minimum
Operating Frequency
50Hz
60Hz
30Hz
35Hz
40Hz
45Hz
11