Outdoor Unit; Installation; Mounting The Outdoor Unit; To Prepare The Installation Structure - Daikin Altherma Split ERLQ004CAV3 Manuel D'installation

Masquer les pouces Voir aussi pour Altherma Split ERLQ004CAV3:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3 Installation

3.2

Mounting the outdoor unit

3.2.1 To prepare the installation structure

If the unit is installed directly on the floor, prepare 4 sets of M8 or M10
anchor bolts, nuts and washers (field supply) as follows:
INFORMATION
The maximum height of the upper protruding part of the bolts
is 15 mm.
(mm)
In order to guarantee good operation of the unit in areas with risk of
snowfall, a minimum of 15 cm needs to be assured below the bottom
plate of the unit. It is recommended to construct a pedestal with the
same height as the maximum snowfall height. On this pedestal it is
then recommended to install the EKFT008CA option kit to guarantee
the minimum space of 15 cm below the bottom plate of the unit.
b
(mm)
a Maximum snowfall height
b EKFT008CA option kit
Installation manual
2
If the unit is installed on brackets to the wall, it is advised to use the
EKFT008CA option kit and to install the unit as follows:
b b
(mm)
a Maximum snowfall height
b EKFT008CA option kit
Daikin Altherma low temperature Split outdoor unit
ERLQ004~008CAV3
4PW73435-1 – 2012.05

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Altherma split erlq006cav3Altherma split erlq008cav3Altherma erlq004cav3Altherma erlq006cav3Altherma erlq008cav3

Table des Matières