5.5
Connecting the hose lines
See chapter "Application example" for an example of how to route the hoses
from the product to the tank.
 Verify that the hoses are resistant to the stored liquid and its vapours.
1. Use oil- and water-resistant plastic hoses 6 x 2 mm for the measuring line
(red), the suction line (transparent) and the pressure line (transparent).
2. In outdoor or underground applications, install the hoses in suitable liquid-
tight, shock-resistant and weather-resistant protective pipes.
3. The hose lines must have the full cross section over the entire length;
there must be no bends and indentations.
4. Do not install any shut-off fittings.
5. During mounting, secure all transition and connection points of the hose
lines by means of hose clamps.
You may also use quick-action couplings (shutting off at one end, for exam-
ple, nominal diameter 7.2, Rectu Base type 26) at the tank side of the pres-
sure line and the measuring line of the interstitial space. The following condi-
tions apply to this:
The coupling part with the shut-off element is directly and permanently
mounted to the tank.
The connection piece for the pressure line and the measuring line is
secured by means of one hose clamp for each hose.
The pressure line and measuring line must be mounted and connected in
such a way as to prevent twisting.
Quick-action couplings enable factory-filling of the interstitial space with dried
air which considerably reduces the time required on site for commissioning.
The following must ensured:
Only dried air may be in the interstitial space.
The coupling part at the tank end must be clean.
Mounting
Europress
EN
29