4.3
Requirements
● AC supply line disconnected and disconnection established
● DC cable disconnected from PV array, or DC no-load voltage under 50V
● PV strings to be connected have been checked for possible ground fault, and existing ground faults have been
eliminated
● DC disconnector on the inverter is switched to the "OFF" position.
● MC4 unlocking tool available for removing the PV cable
4.4
Connecting
Connection diagram
Grounding
The SINVERT PVM inverter must be grounded. Otherwise a potential difference can build up, causing an electric shock
hazard.
● Cable cross-section for grounding greater than cross-section of mains supply conductor (at least 10 mm²)
● Lay grounding cable as far as possible from mains supply conductor. (affected by faults)