Technical Data; Actuator Dimension Drawing Ema Dwv; Dwv 3-Way Reversing Valve Dimension Drawing - Dimplex DWV 25 Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DWV 25 - EMA DWV
4

Technical data

4.1 Actuator dimension drawing
EMA DWV
Technical description
Synchronous motor with electronic activation and switch-off
Electronic end position detection and motor switch-off via
time switch in device (60 s)
Maintenance-free gearbox with magnetic clutch
Gearbox can be disengaged for positioning the reversing valve manually
(with hand lever)
Two-part housing made of self-extinguishing plastic
Console and bayonet ring made of glass fibre-reinforced plastic for
Mounting on the reversing valve
Connection cable length 1.2 m, 3 x 0.75 mm²
Runtime for 90° rotation angle is 30 s
Max. temperature of medium 100 °C
Permissible ambient temperature -10...55 °C
Permissible ambient humidity 5...95 % r.h. without condensation
Degree of protection (horizontal) IP 54
Protection class II in accordance with IEC 60730
Minimum response time 200 ms
Mounting position: vertically to horizontally, but not upside down
Type
Regulation
EMA DWV
2 / 3-point

4.2 DWV 3-way reversing valve dimension drawing

A
DN
mm
25
21
32
24
40
28
50
34
Runtime
Rotation angle
120 s
90°
B
c
mm
mm
45
31
53
34
57
40
69
53
GDD-DWV · FD 9612
Voltage
230 V~, 50...60 Hz
General parameters
Nominal pressure
Nominal width
Leakage rate passage
Leakage rate bypass
Rotation angle
Ambient conditions
Operating temperature
Operating pressure
L
G
mm
85
Rp 1"
99
Rp 1 1/4"
110
Rp 1 1/2"
131
Rp 2"
English
Power consumption
2.4 W 4.5 VA
40 bar
DN 25 - DN 50
0.0001 x k
value
vs
0.0001 x k
value
vs
90°
-10...130°C without condensation
40 bar (-10...50'°C)
35 bar (130 °C)
kvs value
H
Control passage
mm
(m³/h)
39
9
48
13
55
25
67
37
EN-9

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Dwv 32Dwv 40Dwv 50Ema dwv

Table des Matières