G
®
PREMASGARD
1140 ⁄ PREMASREG
Quality product for HVAC sector, accuracy ± 1.5 % or ± 3 %
The calibrateable compact pressure sensors PREMASGARD
ally with or without display (eight devices in one) and are used for measuring above-atmospheric, below- atmospheric, or differential pressures in air.
The piezo-resistive measuring element is temperature-compensated and guarantees a high degree of reliability and accuracy. These pressure
transmitters have a pushbutton for manual zero point calibration and an adjustable offset. Applications of these pressure sensors are in clean room,
medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level
measurement or for triggering frequency converters. Media measured with these pressure transducers are air (non-precipitating), or other gaseous
non- ggressive, non-combustible media. A PREMASGARD
minimizes the diversity of types and stockkeeping while covering a greater range of applications. The differential pressure sensor is supplied including
connection set ASD -06 (2 m connection hose, two pressure connection nipples, screws).
Electronic pressure sensors and switches PREMASREG
continuous output, and a display for setting the switchpoint and to display the ACTUAL pressure (eight devices in one plus differential pressure
switch ⁄ differential pressure monitor and continuous pressure sensor in one and the same device). The pressure sensor is used for above-atmos-
pheric, below-atmospheric, or differential pressure measurement in clean air with limit value switching. The piezo-resistive measuring element
guarantees a high degree of reliability and accuracy. Applications of these pressure sensors are in clean room, medical and filter technology, in
ventilation and air conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement or for triggering
frequency converters. Media measured with these pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-
combustible media. The pressure sensor PREMASREG
switchpoint correction. Fine adjustment by the user is possible at any time. A connection set ASD-06 (2 m connection hose, two pressure connection
nipples, screws) is included in the scope of supply.
TECHNICAL DATA:
Power consumption: ..................... < 1 VA ⁄ 24 V DC, < 2.2 VA ⁄ 24 V AC
Measuring ranges: ......................... multi-range switching with 8 switchable measuring ranges
Media temperature: ...................... 0 ... + 50 °C
Pressure connection: .................... 4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm), metal pressure connection nozzles
Type of pressure: ........................... differential pressure
Above- ⁄ below-
atmospheric pressure: ................. max. ± 200 hPa
Signal filtering: ................................ switchable 1 s ⁄ 10 s
Medium: ........................................... clean air and other non-aggressive,
®
PREMASGARD
1140
Power supply: ................................. 24 V AC (± 20 %) and 15 ... 36 V DC (± 10 %) for U variant
Output signal: ................................. 0 -10 V or 4 ... 20 mA
Electrical connection: ................... 2- or 3-wire connection
Accuracy: ........................................ ± 1.5 % of final value (at 20°C) with display (not ± 100 ⁄ 50 Pa)
Sum of Linearity + hysteresis: ..... < ± 1 % of final value with display
Temperature drift values: ............. ± 0.1 % ⁄ °C with display
Zero point offset: ........................... < ± 0.7 % of final value with display
®
PREMASREG
1141
Power supply: ................................. 24 V AC ⁄ DC (± 20 %)
Output signal: ................................. 0 -10 V, 1 changeover contact (24 V ⁄ 1 A)
Electrical connection: ................... 3-wire connection (U)
Accuracy: ........................................ ± 1.5 % of final value (at 20°C)
Sum of Linearity + hysteresis: ..... < ± 1 % of final value
Temperature drift values: ............. ± 0.1 % per °C
Zero point offset: ........................... < ± 0.7 % of final value
Enclosure: ........................................ impact-resistant plastic, material polyamide, 30 % glass-globe-reinforced, with quick-locking screws,
Dimensions: ..................................... 108 x 70 x 73.5 mm (Thor II)
Electrical connection: .................... 0.14 - 1.5 mm², via removable plug-in screw terminals
Cable gland: ..................................... M 16, including strain relief
Humidity: .......................................... < 95 % r.H., non-precipitating air
Protection class: ............................ III (according to EN 60 730)
Protection type: ............................. IP 65 (according to EN 60 529)
Standards: ....................................... CE conformity, according to EMC directive 2004 ⁄ 108 ⁄ EC,
Features: ......................................... two-line display with illumination, cutout ca. 36 x15 mm (W x H),
ACCESSORIES: ............................... including connection set ASD - 06 (nipple straight) – (included in the scope of delivery)
®
1141
®
®
1140 series pressure sensor has eight selectable measuring ranges and therefore,
®
1141 are equipped with eight switchable measuring ranges, one switching output and one
®
1141 has a manual zero point pushbutton and an offset potentiometer for final value and
see table
non-combustible gases
15 ... 36 V DC (± 10 %) stabilised, max. ripple 0.5 Vss for I variant (depending on working resistance)
± 3.0 % of final value (at 20°C) without display
(optional ± 1.5 % of final value)
< ± 2 % of final value without display, standard
(optional ± 1 % of final value)
± 0.3 % ⁄ °C without display
< ± 1.5 % of final value without display
colour pure white (similar RAL 9010)
according to EN 61326-1: 2006, according to EN 61326-2-3: 2006
for displaying ACTUAL pressure and ⁄ or SETPOINT pressure respectively undercutting
or exceeding the measuring range
connection nipple ASD - 07 (at 90 degree angle)
pressure outlet DAL -1 for ceiling or in-wall installation (e.g. in clean rooms)
of the 1140 series are equipped with eight switchable measuring ranges and option-
10