Minilux PIR 41-270 Sensor
Fitting and operating instructions
1. Application
The Minilux PIR 41-270 Sensor is used in connection
with the Minilux Control/Luxstat Control for lighting
control.
Areas where lighting control can be of benefit:
- Corridors
- Office premises
- Canteens
- Lounges
- Toilets
2. Function
The PIR 41-270 Sensor does not have an in-built
light sensor
Depending on which kind of Controller is connected,
the Minilux PIR 41-270 Sensor turns on the light in
the room. The light is turned off automatically after a
preset period, when the PIR 41-270 Sensor does not
detect activity in the coverage area.
3. Installation
Location:
The sensors respond to heat and movement in
relation to the surroundings.
The sensors are most sensitive when movements
(direction of walking) take place diagonally or across
the "beams". Figs. 1 and 2
Avoid locating close to "heat sources": cookers,
electric radiators, ventilation systems, mobiles, etc.
These can cause unwanted activation. Fig. 4
To open the sensor: Insert screwdriver into recess
and turn. Fig. 7G.
Fitting:
The sensors are designed to be fitted in a Euroformat
box. Figs. 7A-7F
Connection:
Example of connection, Fig. 3.
Parallel connection of sensors (max. 8), Fig. 3a.
Max. length of cable to Minilux Control: 200 m with
2 x 2 x 0.6 mm.
4. Settings
After connection to the power supply, PIR Sensors
are ready for operation after 1-2 min. (warm-up time).
The range at 90° and 40° respectively is shown in
Figs. 5 and 6
5. Troubleshooting
Problem:
PIR 41-270 Sensor fails to switch on
1. Incorrect connection
2. The sensor does not receive any power supply
(24V on terminals 1 and 2)
3. Lux level on the Controller is incorrect.
No/poor detection in walk test
1. Incorrect location.
2. The lens is covered/dirty or defective
6. Maintenance
Dirt affects the operation of the sensor and the
sensor's lens must therefore be kept clean. Use a
damp cloth for cleaning. Use water with a standard
detergent. Avoid pressing hard on the lens in the
front.
If the lens or other parts of the sensor are defective,
the sensor must be replaced.
7. Technical data
Input:
Supply voltage ................................. 24VDC ±10%
Power consumption:
Worst case ....................................... <5mA (24VDC)
Standby ............................................ <3mA (24VDC)
Output:
Max. current load ............................ 50mA (24VDC)
Output signal ................................... ON/OFF, NPN
Performance:
Range .............................................. 90°, 5m
Protection class ............................... IP 20
Ambient temp. ................................. -20°C..+50°C
Approvals:
CE accordig to ................................. EN 60669-2-1
Possible cause:
Proposed solution:
1. Check that the sensor is connected as shown in
Fig. 3
2. Check that the Controller is connected correctly.
3. Check that the Controller is set correctly.
1. Position the sensor as shown in Figs. 1, 2, 5 and
6
2. Remove the cover/clean the sensor as described
in item 6. If the lens is defective, the sensor must
be replaced.
8. Accessories
Box for:
- masonry wall ................................. 54-903
- sheet wall ...................................... 54-904
- plate mounting .............................. 54-905
Angle bracket for 54-905 ................ 54-906
4(6)