STANDARD PROGRAMMING
1
Power Supply
Give power supply, the display shows the following symbols "
*
If the control panel has already been programmed and the power fails or is switched off - once power is returned and a START com-
mand is given, the position reset procedure is performed (see "rESP" in the table "WORKING STATUS MESSAGES" on page 68.
2
Visualisation of inputs and operations-counter status
1. Press the
key for 15 seconds;
2. The display will show respectively:
Inputs status (check it's correct);
Total operations counter (* see P064):
i.g.:
= 3x100* = 3000 operations performed
Maintenance operations-counter (* see P065):
i.g.:
= 5*x500 = 2500 operations remaining
before the maintenance intervention request (
manoeuvres-counter disabled)
3. Hold down the
key to display a cyclic 3 options, or
release the
button to exit the parameter.
3
Selection type of operators
1. Scroll down the parameters with
sualise P028;
2. Access the parameter by pressing the
3. Acting on
and
keys, set:
- d003=PASS;
- d004=STOP;
4. Confirm your choice by pressing the
again to P028).
4
Selection operating with or without encoder
Warning: Remember to correctly set the jumpers J5 and J9.
A
A
A position = operators with encoder (remind to set P029=0)
B
B
B position = operators without encoder (remind to set P029=1)
1. Scroll down the parameters with
sualise P029;
2. Access the parameter by pressing the
3. Acting on
and
keys, set:
- d000=for operators with encoder;
- d001=for operators without encoder;
4. Confirm your choice by pressing the
again to P029).
", "
=
! IMPORTANT !
and
keys until you vi-
key;
key (display returns
and
keys until you vi-
key;
key (display returns
", "
" and then "----".
! IMPORTANT !
59