EN
RWF 50/55
- Microprocessor regulator - Setting parameters PArA
Parameter
Proportional band
¹
Derivative time
Integral action time
Dead band (neutral
zone) ¹
Controlling element
running time
Switch-on threshold
Heating controller ¹
Switch-off threshold
stage II
Heating controller ¹
Switch-off threshold
Heating controller ¹
Response threshold
Outside temperature
Curve point1 ¹
Boiler temperature
Curve point 1 ¹
Outside temperature
Curve point 2 ¹
Boiler temperature
Curve point 2 ¹
Note! When using the RWF50... as a modulating controller only, or as a modulating controller without the burner
release function (1P, 1N), parameter HYS1 must be set to 0 and parameters HYS2 and HYS3 must be set to their maximum values.
Otherwise, for example, when using default parameter HYS1 (factory setting -5), the 3- position controller is only released
when the control deviation reaches -5 K.
12
www.ecoflam-burners.com
Display Value range
1...9999 digit
Pb1
0...9999 s
dt
0...9999 s
r t
b
0,0...999,9 digit
db
10...3000 s
t t
HYS1 1999...0,0 digit
HYS2 0,0... HYS3 digit
HYS3 0,0...9999 digit
q
0,0...999,9
Set 55.2 Ecoflam (external probe)
At 1
-40......120
Ht 1
SPL......SPH
At 2
-40......120
Ht 2
SPL......SPH
¹ Setting of decimal place has an impact on this parameter.
Factory
Set 50.2/55.2
Ecoflam
setting
(passive probe)
FT-TP/1000
10
8
80
60
350
180
1
1
15
15
-5
-5
3
3
5
5
0
0
- 10
-10
60
68
20
22
50
48
Set 50.2/55.2
Ecoflam
(active probe)
QBE...- P...
0,1
50
180
0,5
15
-0,5
3
1
0
-10
68
22
48
420010571400