RWF 50/55
- Microprocessor regulator - Setting parameters PArA
The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the deriva-
tive action time dt and the integral action time rt.
To change parameters Pb1, dt, rt, proceeds as follows: - Press the
button, appare nel display di base
can be increased or decreased using the keys tand s (see table), press
parameter. - When dt is displayed, repeat the procedure described above. - Press
rt is displayed, repeat the procedure described above. - To return to normal display press
DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFF.
The regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.
HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power. HYS3 indicates
the upper shutoff limit, above which the regulator switches the burner off. To set HYS1 and HYS3 proceed as follows:
- Press the
Enter button to access the parameters level
Enter
is displayed (burner ignition differential-stage II), increase or decrease the value using the t and s keys. - Confirm the changed para-
meters by pressing
Enter button. - Press
Enter
rential-stage II), repeat the procedure described above. - Press
displayed (upper shutoff differential) repeat the procedure described above. - To return to normal display press
MANUAL/AUTOMATIC MODE
To access "MANUAL" mode, press and hold
ration. It is deactivated automatically when the burner shuts off. When the
the position of the servocontrol can be changed using the t and s keys. The LEDS on the front of the regulator indicate whether the
servocontrol OPEN or CLOSE command is currently active. Pressing the s key the servocontrol OPENS. Pressing the t key the ser-
vocontrol CLOSES. To select automatic mode press and hold
and the regulator reverts to automatic.
RESPONSE THRESHOLD (q)
The response threshold (q) defines for what period of time and how much the actual value is allowed to drop before the system swit-
ches to high-fire operation.
An internal mathematical calculation using an integration function determines the sum of all areas qeff = q1 + q2 + q3 as shown in the
graph. This takes place only when the control deviation (x-w) falls below the value of switch-on threshold HYS1. If the actual
value increases, integration is stopped.
If qeff exceeds the preset response threshold (q) (can be adjusted at the parameter level), this causes the second burner stage to
switch on or – in the case of the 3- position controller/modulating controller – the controlling element to open.
If the current boiler temperature reaches the required setpoint, qeff is reset to 0.
Temperatura (°C)
Temperature
420010571400
PArA. - To move from one parameter to the next, press
PArA
PArA. - To move from one parameter to the next, press
PArA
Enter button, to access the next parameter. - When HYS2 is displayed (burner shutoff diffe-
Enter
ESC for at least 5 seconds. Manual mode can only be selected when the burner is in ope-
ESC
ESC for at least 5 seconds.. The LED above
ESC
q
7866d09it/0712
Enter button to access the parameters level
Enter
Enter. - When Pb1 is displayed, the value
Enter
Enter to confirm. - Press
Enter
Enter button, to access the next parameter. - When
Enter
ESC.
ESC
Enter button, to access the next parameter. - When HYS3 is
Enter
HAnd symbol is alight, the regulator is in manual mode and
HAnd
q
q
OPr, Press the t
OPr,
Enter button, to access the next
Enter
Enter. - When HYS1
Enter
ESC.
ESC
HAnd symbol, goes out
HAnd
q
www.ecoflam-burners.com
EN
11