Please be sure to always follow this procedure in the following sequence:
Set the DIP switches according to the load switch function
Mount MPS on DIN rail or wall
Connect the load wiring to the unit with proper polarity.
Connect the battery wiring to the unit with proper polarity.
When disassembling perform the installation sequence in reverse order.
Note: Changes to DIP switches after connecting the unit to the battery do not affect the function
of the unit.
1.2.1 Setup DIP switches
The MPS comes with an 8 pole DIP-switch, which can be used to set up your MPS.
ON
OFF
1
Adjust the DIP switch settings according to load switch function:
DIP NO.
DIP 8
DIP 7
DIP 6
DIP 5
DIP 1
OFF
ON
OFF
ON
X
1.3 Installation instruction
1.3.1 Wall mounting
Please see fig 1, 2 and 3 which shows how to install the MPS controller on a standard 35mm DIN
Rail.
Make sure that the ventilation slits on the sides are unobstructed.
2
3
4
5
Setting
OFF
Activates MPS as load switch/deep discharge protection
Unused
X
X
Unused
Stand-alone function
OFF
DIP 3
DIP 2
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
X
ON
SAB
6
7
8
Function
LVD level
Level 1 (11.0V)
Level 2 (11.25V)
Level 3 (11.5V)
Level 4 (11.75V)
Level 5 (12.0V)
23
ON
OFF