Wilo Star RS Notice De Montage Et De Mise En Service page 20

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 21
ENGLISH
8 Problems, Causes
and Remedies
Motor is switched on but fails to
run:
– Check electrical fuses,
– Check voltage of pump (observe
rating plate data),
– Check
capacitor
rating plate data!).
– Motor is blocked, e.g. by deposits
from the heating water.
– Remedies: Fully remove vent plug,
check and if necessary rectify free
running of pump rotor by turning
the slotted end of the shaft with a
screwdriver (Fig. 9).
At high water temperatures
and system pressure close
isolating valves before and
after the pump. First, allow
pump to cool down
Noisy pump operation
– Cavitation due to insufficient inlet
pressure.
– Remedies: increase system pressu-
re within the permissible range.
– Check speed setting, if necessary
switch to a lower speed.
If the fault cannot be rectified,
contact
your
Customer Service.
9 Spare parts
All rating plate data must be stated
when ordering spare parts.
20
All manuals and user guides at all-guides.com
size
(observe
nearest
WILO
Subject to technical alterations!

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Star rsdStar stStar rsgStar ac

Table des Matières