FD113 uses the pressure differential between the 2
inputs to operate an electrical switch. For application
in
refrigeration
and
air-conditioning
according to EN378. E.g. Compressor oil pressure
control.
!
Safety instructions:
• Read
installation
instructions
Failure to comply can result in device failure,
system damage or personal injury.
• It is intended for use by persons having the
appropriate knowledge and skill.
• Before opening any system make sure pressure
in system is brought to and remains at
atmospheric pressure.
• Ensure supply voltage and current of electric
device match rating on FD113 name plate.
Disconnect supply voltage from system and
FD113 before installation or service.
• Do not exceed test pressure.
• Keep temperatures within nominal limits.
• Do not apply torsional force to switch housing
assembly during assembly (Fig. 5).
Differential Pressure Setting: (Fig. 0 - 2)
The cut-out pressure can be adjusted between 0.3 bar
and 4.5 bar (factory setting: 0.7 bar). Cut-in pressure
is fixed 0.2 bar above cut-out pressure.
Reset:
FD113 and FD113A are automatically reset, FD113
ZU have to be manually reset with the reset button
(Fig.0 - 3).
Time Delay Setting (FD113(A) ZU only):
The Time delay is continuously adjustable between
20 and 150 s (see Fig. 0 - 4).
Function / Type of switch (see Fig. 1):
Differential pressure controls.
Mounting direction:
FD113 can be mounted in any direction, preferably
with pressure connections vertically.
Pressure connection (see Fig. 5):
Apply Teflon sealant to adapter thread.
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Operating instruction
Differential Pressure Controls Series FD113
Leakage test:
After completion of installation, a test pressure must
systems
be carried out as follows:
- According to EN378 for systems which must
comply with European pressure equipment directive
97/23/EC
- To maximum working pressure of system for other
applications
thoroughly.
Warning:
- Failure to do so could result in loss of refrigerant
and personal injury.
- The pressure test must be conducted by skilled
persons with due respect regarding the danger related
to pressure.
Maintenance/Service:
In case of repair work or replacing the control always
use new sealant.
Electrical connection (Fig. 1, 2, 3, 4):
Note: Comply with local electrical regulations
when wiring. Wire size must be suitable for electric
device connected to the FD113.
Wiring FD113 ZU, FD113A ZU (acc. to Fig. 3
or 4):
A Thermal overload relay (motor protection)
B
Motor fuses
C
Control circuit fuse gL, max. 4 A
D Differential pressure control
T
Thermostat
H Indicator lamp "Oil pressure"
I
Indicator lamp "Fault"
K Compressor contactor
M Compressor motor
Test FD113, FD113A:
Pushing lever 1 (Fig. 0) upwards simulates a pressure
rise at the HP side. Pushing lever down during
operation simulates a lack of HP.
Test FD113 ZU, FD113A ZU:
When testing "Fault-circuit" = low oil pressure,
observe safety precautions.
Use screwdriver to press lever 1 (Fig. 0) for the delay
time-setting (>20s ... >150s) to the lower stop.
The test is to be repeated occasionally, being carried
out when regular plant inspections takes place. After
tripping, reset with button 3 (Fig 0).
www.emersonclimate.eu
Technical data:
• Max. differential pressure PS: 12 bar
• Test pressure PT:
• Electrical rating:
Inductive (AC):
Inductive (DC):
• Nominal Voltage (FD113ZU only):
• Protection class (EN 60529):
• Ambient temperature:
• Vibration resistance:
• Medium compatibility:
• Marking: CE according to Low Voltage Directive
• Marking:
Type code:
FD113
FD113A
FD113 ZU
FD113A ZU
FD113 (A22-057) Copeland version with fixed time
Pressure connections:
• 7/16"-20 UNF male (standard version)
• G1/4" female brass
• 1 m capillary with flare nut 7/16"-20 UNF
• G1/4" male steel
Accessories:
Capillary tube 1,5m (Fig.6)
Mounting bracket, angle (Fig. 7)
Mounting plate (Fig. 8)
Extension bracket (Fig. 9)
Copper Gasket Set R1/4" (100pcs)
Date: 22.06.2016
25 bar
3 A @ 230 V AC
0.1A @ 230 V DC
24 ... 240 V AC / DC
IP30
-20°C to +70°C
4g (10...1000 Hz)
HFC, HCFC
std version with brass connector
std version with steel connector
version with time delay and brass
connector
version with time delay and steel
connector
delay of 115 sec and fixed cut-
out setting of 0.63 bar
Part No.
803 804
803 799
803 801
803 800
803 780
FD113_OI_ML_R07_0716121.docx