Installing the stove
The floor on which the stove is installed must be
even and horizontal. The stove may only be in-
stalled on an adequate load-bearing floor. The
stove can be stood on a metal floor sheet or glass
sheet to protect the flooring.
If the flooring or carpet is inflammable, a stable
and non-combustible spark protection plate must
be used. This must extend 50 cm to the front and
30 cm to each side beyond the edge of the com-
bustion chamber opening. Under the stove no
spark protection plate is required.
Asembly sequence
● If intended, install the OEC.
● The Ø150mm stovepipe connection can be in-
stalled at the top or rear. The stove is supplied
ready for connec- tion from above. If you wish to
connect it at the rear, the following steps must be
carried out to make the necessary modifications:
‐ Break out the cover in the back panel.
‐ Replace the connector sleeve and the sealing
cover.
● Decide where the stove is to be installed. There
must be no objects made of combustible materials
within a dis- tance of 80 cm of the stove‟s radiation
area, measured from the combustion chamber‟s in-
spection glass, nor may any be placed within this
area subsequently.
Depending on the
installation
stove in front of walls that need to be protected
(flammable or load-bearing), the following dis-
tances from walls need to be observed in ac-
cordance with the position of the combustion
chamber door to the wall / side panel or the back
panel (see schematic diagram).
When not dealing with walls that need to be protect-
ed, you merely need to observe a minimum dis-
tance of approx. 5 cm to allow for proper heat dissi-
pation.
If the stove is set up with the turntable, then the
turnta- ble must be positioned in such a manner
that the radi- ation area of the glass pane cannot
be turned in the di- rection of components
must be protected, or the distance must be
least 80 cm.
● Install the pipe lining (provided on site) in the
chimney. The connection height can be individu-
ally specified for a top stovepipe connection, how-
ever should not exceed
1.5 m from the connector sleeve. For the rear
stovepipe connection heights please refer the
"Technical Data" chapter. No combustible material
is permitted within a radius of 20 cm around the
stove pipe.
● Connect the stovepipe at both connection points
with stove putty so that the stove pipe is perma-
nently sealed.
● Push the stove onto its planned position and orient
it so that the stovepipe fits into the pipe lining.
The stovepipe connections must be tight. The
stove- pipe must not protrude into the chim-
ney.
position
of
the
that
at
A
Stove installed straight in corner
15
Stove installed diagonally in corner
Bear in mind that on partition walls in accordance
with test specification EN 13240 the temperature
of 85°C can be reached, and with light wallpaper
or similar combustible construction materials
this can result in colour changes.
A
15