Specifications; General; Characteristics; Ac Current (Automatic Ranges) - Chauvin Arnoux F 62 Notice De Fonctionnement

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
English
5.

SPECIFICATIONS

5.1. General

Only values with tolerances or stated limits are
guaranteed. Values without tolerances are stated for
information only.

5.2. Characteristics

The precision is ± [% of reading (L) + number of
representation units (digits or D)] under the reference
conditions (see Appendix).

5.2.1. AC current (automatic ranges)

Ranges
Resolution
1.2%±5cts(50~60Hz)
10A
1mA
2.5%±5cts(60~500Hz)
80A
10mA
F 65 : 3.5%±10cts (500~3kHz)
80~100A
10mA
5%±5 cts (50~60Hz)
Overload protection: 150 A
rms
F65: RMS measurement (Rooth Mean Square value)

5.2.2. mAC current (automatic ranges)

Ranges
Resolution
1.2%±5cts(50~60Hz)
60mA
10µA
2.5%±5cts(60~500Hz)
600mA
100µA
F 65 : 3.5%±10cts (500~3kHz)
Overload protection: 150 A
rms
F65: RMS measurement (Rooth Mean Square value)

5.2.3. AC voltage (automatic ranges)

Ranges
Resolution
1.0%±5cts (50~60Hz)
600V
0.1V
1.2%±5cts (60~500Hz)
F 65 : 2.5%±5cts (500~3kHz)
Input impedance: 1 MΩ
Overload protection: 660 Vrms
F65: RMS measurement (Rooth Mean Square value)

5.2.4. DC voltage (automatic ranges)

Ranges
Resolution
600V
0.1V
1.0%±2cts
Input impedance: 1 MΩ
Overload protection: 660 Vrms
F65: RMS measurement (Rooth Mean Square value)
33
Accuracy
Accuracy
Accuracy
Accuracy
F 62 – F 65

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

F 65

Table des Matières