4.2. Leakage current measurement (mA range)

Load
600V CAT
III
100A
Press 2 Sec
HOLD
50 / 60Hz
OFF
A
mA
V
V
Hz
PEAK
ZERO
600V
Note: As a safety measure, disconnect the measuring
cords from the clamp before performing this operation.
The measurement is optimal with the conductor centred
in the middle of the jaws.
Set the switch to mA~.
Open the clamp by pressing the trigger.
Place the clamp around the active conductors (Phase
conductors and Neutral) and release the trigger; check
that the clamp is properly closed. Read the measurement
on the display unit.
The reading can be filtered to reflect only the fundamental
by a long press on the HOLD key, giving an indication of
the impact of the harmonics.
29
F 62 – F 65