7.6 P3 menu - Secondary line voltage control
Setup
P3.01
P3.02
The highlighted
P3.03
parameters are
included only in
P3.04
version 261 94
P3.05
P3.06
P3.07
P3.08
Note:
For
P3.09
explanations
on the opera-
P3.10
tion
of
P3.11
parameters,
see previous
P3.12
page
con-
P3.13
cerning the
main
line
P3.14
menu.
P3.15
Description
Minimum voltage threshold - release
Minimum voltage threshold - retrieval
Minimum voltage threshold delay
Maximum voltage threshold - release
Maximum voltage threshold - retrieval
Maximum voltage threshold delay
Threshold of phase failure
Phase failure threshold delay
Voltage unbalance threshold
Voltage unbalance threshold delay
Threshold of minimum frequency
Minimum frequency threshold delay
Threshold of maximum frequency
Maximum frequency threshold delay
Voltage delay of secondary line within the limits
Range
70...98 % Ue
75...100 % Ue
0.1 .... 900 s
102...120 % Ue / OFF
100...115 % Ue
0.1 .... 900 s
60 ... 85% Ue / OFF
0.1 ... 30.0 s
1 ... 20 % / OFF
0.1 ... 900 s
99 ... 80 % Fe / OFF
0.1 ... 900 s
101 ... 120% Fe / OFF
0.1 ... 900 s
1 ... 3600 s
Default
85 % Ue
90 % Ue
1.0 s
115 % Ue
110 % Ue
1.0 s
70 % Ue
0.1 s
10 %
5.0 s
95 % Fe
5.0 s
105 % Fe
3.0 s
20 s