7.4 P1 menu - General data
Setup
P1.01
The highlighted
P1.02
parameters are
included only in
version 261 94
P1.03
P1.04
P1.05
P1.06
P1.07
P1.08
P1.09
P1.10
P1.11
P1.01 - Determines the type of commutation (utility-to-utility/utility-to-generator)
P1.04 - If, after sending an opening or closing command to a switch, it does not place itself correctly within this time,
P1.05 - Enable the control only if their contacts are wired
P1.06 - If both sources are simultaneously unavailable in automatic mode for a period of time longer than P1.06, the
P1.07 - Time between the line failure used below and transmission of the startup signal to the generator on the secondary
P1.08 - Time whereby the generator is left in operation in order to cool down after being disconnected from the load
Description
Type of application
Control of phase sequence
Changeover control
Circuit breakers Timeout
Enable control of withdrawn
Maximum time load not powered (A07 alarm delay)
Startup delay time, generator
Cooling time, generator
Minimum battery voltage threshold
Maximum battery voltage threshold
Battery threshold delay time
the A03 or A04 alarms will be generated
A07 alarm will be generated
line.
It is a time which is independent from the circuit breaker opening time
Range
U-G = Utility-to-Generator
U-U = Utility-to-Utility
OFF - Disabled
123 - Direct
321 - Opposite
FEE - With feedback
NOF - Without feedback
OFF / 1...900s
OFF (Control disabled)
(Control enabled)
ON
OFF / 1...3600s
0 .... 900 s
1...3600s
OFF / 70...100%
OFF / 110...140%
0...60 s
Default
U-G
OFF
FEE
5 s
OFF
OFF
1 s
120 s
75%
130%
10 s
17