Installation Instructions
Please Leave for Occupant
Important Notes
Please read before installing.
1. Install in accordance with national and local electrical codes.
NOTICE: To avoid damage to dimmer and/or equipment, use only
approved loads. See table for details.
2.
When no "grounding means" exists within the wallbox for an existing
switch or dimmer, the 2011 National Electrical Code (NEC
switch/dimmer to be installed as a replacement as long as 1) a nonmetallic,
noncombustible faceplate is used with nonmetallic attachment screws or
2) the circuit is protected by a ground fault circuit interrupter. The 2008
NEC
has the same allowances but does not contain the requirement
®
for nonmetallic attachment screws.  When installing a switch /dimmer
according to any of these methods, cap or remove the green wire before
screwing the switch/dimmer into the wallbox.
3. These controls are designed to operate in ambient temperatures from 32 °F
to 104 °F (0 °C to 40 °C)
4. Strip wallbox wires. Important: When making wire connections, follow
the recommended strip lengths and combinations for the supplied wire
connectors. Twist wire connector tight making sure that no bare wire is
exposed. Note: Wire connectors provided are suitable for copper wire only.
For aluminum wire, consult an electrician.
5. Some dimmers require a neutral wire in the wallbox. If a neutral wire is not
present, contact a licensed electrician for installation. See wiring diagrams
and table for details.
6. Check for short circuits in new installations before wiring controls. With
power OFF, use standard switch and connect to lamp and voltage line. Turn
power ON. If breaker trips, a short is present. Correct wiring and check circuit
again. Install control only when short is no longer present.
7. Multiphase applications: Use a separate neutral for each phase containing a
control circuit. For more information, refer to Application Note 17, "Common
Neutral Interaction," P/N 048017, at www.lutron.com.
8. For best dimming performance, fluorescent lamps may need to be operated
at full light output for a specified amount of time prior to dimming. Contact
the lamp manufacturer for their specific recommendations concerning lamp
seasoning.
9. To clean, wipe with a clean damp cloth. DO NOT use any chemical cleaning
solutions.
Operation
Slide-to-Off Controls: Raise slider to increase light intensity. Lower slider to
decrease light intensity and turn off.
Preset Dimmers: Push button in center of slider to alternately turn lights on
to preset level (set by slider) or turn lights off. Raise slider to increase light
intensity. Lower slider to decrease light intensity. Push button again to turn
lights off.
3-Way and 4-Way Switches: When switching power from remote location,
lights will turn on to level set on dimmer (by slider), or turn off. Move slider
up or down to turn lights on or off. Note: Use only one dimmer per circuit.
Incandescent Dimmers NT- Series
Magnetic Low-Voltage Dimmers NTLV- Series
P/N 0301842a
Electronic Low-Voltage Dimmers NTELV- Series
Fan-Speed Controls NTFS- Series
Quiet Fan-Speed Controls NTFSQ- Series
Fluorescent Dimmers NTF- and NTFTU- Series
Installation
If more than one control is to be installed in the same wallbox, review the
Multigang Installation section before beginning. Lutron multigang faceplates
are available for ganging multiple units.
1.
) allows a
®
2. Remove faceplate and faceplate adapter (if applicable) from control to
prevent damage and to access mounting holes. Pull from top of faceplate to
remove. Unscrew faceplate adapter. Set aside.
3. Wire control per appropriate wiring diagram (see table on next page) using
wire connectors provided.
Note: Color names refer to the wire colors on the control.
4. Push wires into wallbox, allowing room for control to be inserted. Do not pinch
wires between wallbox and control.
5. Mount control to wallbox using control mounting screws provided. Controls
must be mounted vertically. See stamp on control for correct positioning.
6. Mount adapter plate with adapter mounting screws provided (see below).
7. Snap on slider and faceplate.
8. Turn power ON at circuit breaker or replace fuse.
Control
Minimum Light Level Adjustment: Dimmers are factory calibrated. Some
dimmers have the ability for low-end adjustment, which is not normally required.
If lamps flicker or drop out at the minimum dimming level there may be an
installation error. Continued use of the system in this mode will cause premature
lamp failure. If this is occurring, call Customer Assistance at
1.844.LUTRON1.
WARNING: Shock Hazard. May result in
serious injury or death. Turn power OFF
at circuit breaker or remove fuse. Damage
to this product caused by wiring with
power on voids the warranty.
Control Mounting
Screws
Faceplate Adapter
Adapter Mounting
Screws
Slider
Faceplate
1

Publicité

loading

Sommaire des Matières pour Lutron NOVA T NT Serie

  • Page 1 Please read before installing. If more than one control is to be installed in the same wallbox, review the Multigang Installation section before beginning. Lutron multigang faceplates 1. Install in accordance with national and local electrical codes. are available for ganging multiple units.
  • Page 2 Magnetic low-voltage dimmers: For more information, see Application Note 19: “Guide to Dimming Low-Voltage Lighting,” P/N 048019, at www.lutron.com. Operation of a dimmed low-voltage circuit with all lamps removed or inoperative may result in current flow in excess of normal levels. To avoid possible transformer failure, Lutron strongly recommends the following: Do not operate dimmed low-voltage circuits without operative lamps in place;...
  • Page 3 Wiring Diagrams Wiring Diagram 1 Wiring Diagram 6 Control Control Cap the second Blue wire (if present) Line/Hot Orange Line/Hot Black Yellow Black Black or Blue Black 120 or 277 V~ Dimming Ballast White 60 Hz Green or 120 V~ Bare (depending 60 Hz...
  • Page 4 (Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.) Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
  • Page 5 Installation à plusieurs compartiments avant 1. Effectuez l'installation en conformité avec les codes électriques en vigueur. de commencer. Des plaques frontales Lutron à plusieurs compartiments sont AVIS : Pour éviter d’endommager le gradateur et/ou l’équipement, utilisez disponibles pour encastrer plusieurs unités.
  • Page 6 CPW0196 Remarques • Gradateurs magnétiques basse-tension : Pour plus d’informations, consultez la note d’application 19 : « Guide de gradation de l’éclairage basse-tension », nº de pièce 048019, sur www.lutron. com. Actionner un circuit basse tension gradué avec toutes les ampoules non fonctionnelles ou retirées peut entraîner une circulation de courant supérieure à un niveau normal. Pour éviter une éventuelle panne du transformateur, Lutron recommande vivement ce qui suit : N’utilisez pas de circuits basse-tension gradués sans ampoules fonctionnelles en place ;...
  • Page 7 Schémas de câblage Schéma de câblage 1 Schéma de câblage 6 Capuchonnez le second fil Commande Commande bleu (le cas échéant) Ligne/ Ligne/ Phase Jaune Orange Noir Phase Noir Noir ou Bleu Rouge Noir 120 ou 277 V~ Ballast de gradation Blanc 60 Hz 120 V~...
  • Page 8 à vous. Autres pays - 1.610.282.3800 Lutron et Nova T* sont des marques déposées de Lutron Electronics Co., Inc., enregistrées aux États-Unis et dans d’autres pays. NEC est une marque déposée de la National Fire Protection Association, Quincy, Massachusetts.
  • Page 9 Instalación de múltiples componentes antes de comenzar. Las 1. Instale según los códigos eléctricos nacionales y locales. placas para dispositivos múltiples de Lutron están disponibles para conectar AVISO: Para evitar daños al atenuador y/o al equipo, sólo utilice en conjunto múltiples unidades.
  • Page 10 Atenuadores magnéticos de bajo voltaje: Para obtener más información, consulte la Nota de aplicación Nº 19: “Guía para atenuar la iluminación de bajo voltaje”, N/P 048019, en www.lutron.com. La operación de un circuito de bajo voltaje atenuado con todas las lámparas retiradas o no operativas podría ocasionar un flujo de corriente superior a los niveles normales.
  • Page 11 Diagramas de Cableado Diagrama de Cableado 1 Diagrama de Cableado 6 Cubra el segundo cable azul Control Control (si lo hubiera) Línea/Vivo Naranja Línea/Vivo Negro Amarillio Negro Negro o Azul Rojo Negro 120 o 277 V~ Balasto de Atenuación Blanco 60 Hz 120 V~ Verde o...
  • Page 12 Fax - 1.610.282.6311 Lutron y Nova T* son marcas de fábrica de Lutron Electronics Co., Inc., registradas en E.U.A. y en otros países. NEC es una marca registrada de la National Fire Protection Association, Quincy, Massachusetts.